Overview
- Use a DC control supply compatible with the 24 V coil and its operating range.
- Match motor voltage and duty to the AC-3, AC-3e or other applicable rating.
- Allow for the integrated NC auxiliary contact in the control schematic.
- Select main-circuit short-circuit protection for the required coordination type.
- Use the specified conductor cross-sections for the spring terminals.
- Maintain the required clearances to neighboring equipment, grounded parts and live parts.
3RT2016-2BB42 SIRIUS S00 9A 24V DC Power Contactor
A size S00 contactor with a 24 V DC coil, spring-loaded terminals and one normally closed auxiliary contact, rated 9 A and 4 kW at 400 V in AC-3/AC-3e service.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 3RT2016-2BB42 |
| Product Type | Power contactor |
| Core Function | Switching three-phase motor circuits |
| Application | Industrial motor starters and control cabinets |
DC control circuit
The coil is rated 24 V DC and uses the standard A1–A2 control terminals.
Normally closed feedback
One instantaneous NC auxiliary contact is integrated.
Spring-loaded connections
Main, auxiliary and control circuits use spring-loaded terminals.
Product Overview
3RT2016-2BB42 switches motor power through three normally open main contacts and provides a built-in normally closed auxiliary contact for the control circuit.
Its compact S00 frame supports 35 mm DIN-rail or screw mounting, while the 24 V DC coil and spring terminals define the control-supply and wiring arrangement.
Key Functions
Switch the rated motor load
AC-3 and AC-3e ratings are 9 A and 4 kW at 400 V, with different current and power limits at other operating voltages.
Return a normally closed auxiliary signal
The integrated instantaneous NC contact gives the control circuit a contact state linked to contactor operation.
Install a compact spring-terminal starter
The 45 mm-wide frame supports screw fixing or a 35 mm DIN rail, with side-by-side mounting and the specified surrounding clearances.
Official Specifications
| Main Contact Arrangement | 3 poles with 3 normally open contacts |
|---|---|
| Frame Size | S00 |
| AC-3 and AC-3e Current | 9 A at 400 V; 7.7 A at 500 V; 6.7 A at 690 V |
| AC-3 and AC-3e Motor Power | 2.2 kW at 230 V; 4 kW at 400 V and 500 V; 5.5 kW at 690 V |
| AC-1 Current up to 690 V | 22 A at 40 °C; 20 A at 60 °C |
| Coil Supply and Operating Range | 24 V DC; 0.8–1.1 times rated voltage |
| Coil Power | 4 W for closing and holding |
| Integrated Auxiliary Contacts | 1 instantaneous NC; no instantaneous NO |
| Auxiliary AC-15 Current | 10 A at 230 V; 3 A at 400 V; 2 A at 500 V; 1 A at 690 V |
| Main and Auxiliary Insulation Voltage | 690 V at pollution degree 3 |
| Main and Auxiliary Impulse Withstand | 6 kV |
| Typical Base-Contactor Mechanical Life | 30 million operating cycles |
| Maximum Switching Frequency | 750 operations/hour in AC-3 and AC-3e; 250 operations/hour in AC-4 |
| DC Operating Delays | Closing: 30–100 ms; opening: 7–13 ms |
| Electrical Termination | Spring-loaded terminals for main, auxiliary and control circuits |
| Connectable Conductor Cross-Section | 0.5–4 mm² solid or stranded; 0.5–2.5 mm² finely stranded |
| Front Degree of Protection | IP20 |
| Ambient Temperature | Operation: −25 to +60 °C; storage: −55 to +80 °C |
| Dimensions (Width × Height × Depth) | 45 × 70 × 73 mm |
| Net Weight | 296.8 g |
Frequently Asked Questions
Can I energize the coil of 3RT2016-2BB42 from a 24 V AC supply?
The coil requires a 24 V DC control supply.
Does 3RT2016-2BB42 include a normally open auxiliary contact?
The integrated auxiliary arrangement is one normally closed contact with no normally open contact.
Can I place 3RT2016-2BB42 directly beside another contactor?
Side-by-side mounting permits zero lateral spacing between contactors while retaining the specified 10 mm front, top and bottom clearance.
Which mounting methods are available for 3RT2016-2BB42?
The contactor supports screw mounting or snap-on mounting to a 35 mm DIN rail.
What motor rating applies to 3RT2016-2BB42 at 400 V?
The AC-3 and AC-3e motor rating at 400 V is 4 kW with a 9 A operational current.
What finely stranded conductor size can I terminate on 3RT2016-2BB42?
The terminals accept finely stranded conductors from 0.5 to 2.5 mm², with or without processed ends.
Which coil-voltage tolerance should I use when supplying 3RT2016-2BB42?
The DC coil operating range is 0.8 to 1.1 times its rated control voltage.