Siemens 3RQ1000-1GB00 SIRIUS 3RQ1 Force-Guided Coupling Relay
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Use the relay within its safety-related switching-off application and appropriate safety circuit.
- Include the required wear-related service-life testing and the 20-year safety mission time.
- Protect NO and NC contact circuits with their different specified gL/gG fuse ratings.
- Use 10 mm conductor stripping length and tighten the screw terminals to 0.6–0.8 N·m.
3RQ1000-1GB00 SIRIUS 3RQ1 Force-Guided Coupling Relay
A monostable 24 V DC coupling relay with two NO contacts, one NC contact and capability up to SIL 2 / PL c.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 3RQ1000-1GB00 |
| Product Type | Coupling relay |
| Core Function | Transferring control signals through relay contacts |
| Application | Safety-related shutdown interfaces |
Couple control commands
The monostable relay uses two normally open contacts and one normally closed contact.
Support safety-related shutdown
The force-guided contacts comply with IEC 60947-5-1 and the defined safe state is shutdown.
Install in compact panels
A 17.5 mm wide housing supports 35 mm DIN-rail or screw mounting and the 3ZY12 device connector.
Product Overview
3RQ1000-1GB00 provides force-guided relay contacts for safety-related switching-off applications.
The industrial enclosure includes an LED and removable screw terminals, with the component rated for use up to SIL 2 and PL c under the applicable safety configuration.
Key Functions
Couple control commands
The monostable relay uses two normally open contacts and one normally closed contact.
Support safety-related shutdown
The force-guided contacts comply with IEC 60947-5-1 and the defined safe state is shutdown.
Install in compact panels
A 17.5 mm wide housing supports 35 mm DIN-rail or screw mounting and the 3ZY12 device connector.
Official Specifications
| Control Supply | 24 V DC; operating factor 0.8–1.2 |
|---|---|
| Active Power Consumption | 0.9 W |
| Contact Arrangement | 2 NO and 1 NC; monostable operation |
| Contact Material | AgNi with gold flash |
| Maximum Thermal Contact Current | 5 A |
| Minimum Output Current | 1 mA |
| AC-15 Contact Rating | 2 A at 250 V AC |
| DC-13 Contact Ratings | 2 A at 24 V DC; 0.2 A at 125 V DC; 0.1 A at 250 V DC |
| Maximum Operating and Release Delays | 15 ms on-delay; 35 ms off-delay |
| Maximum Switching Frequency | 360 operations per hour |
| Required Contact Fuses | NO contacts: 6 A gL/gG; NC contact: 4 A gL/gG |
| Rated Insulation and Impulse Voltages | 300 V at overvoltage category III, pollution degree 3; 4 kV impulse withstand |
| Safety Capability | SIL 2; PL c; category 1 |
| PFHD | 6 × 10⁻⁷ per hour |
| Safety Mission Time | 20 years |
| Mechanical Endurance | 10 million operating cycles typical |
| Terminal Wiring | Removable screw terminals; 10 mm stripping length |
| Terminal Tightening Torque | 0.6–0.8 N·m |
| Operating Temperature | −25 to +60 °C |
| Dimensions and Net Weight | 17.5 × 100 × 120 mm; 0.142 kg |
Frequently Asked Questions
Can 3RQ1000-1GB00 be used for a safety-related switching-on function?
The relay is suitable for safety-related switching off but not safety-related switching on.
Which contact arrangement does 3RQ1000-1GB00 provide for the shutdown interface?
The relay has two force-guided normally open contacts and one force-guided normally closed contact.
What safety capability can 3RQ1000-1GB00 support in the appropriate circuit?
The component is rated up to SIL 2 and PL c with category 1.
Do I need to include contact-wear testing when applying 3RQ1000-1GB00?
Wear-related service-life testing is required for this relay.
Should the NO and NC circuits of 3RQ1000-1GB00 use the same fuse size?
The required gL/gG fuse is 6 A for the NO contacts and 4 A for the NC contact.
Can I distribute the supply to 3RQ1000-1GB00 through a 3ZY12 device connector?
The relay supports operation with the 3ZY12 device connector.
How long can 3RQ1000-1GB00 take to release after the control signal is removed?
The specified maximum off-delay is 35 ms.