Siemens 3RQ1000-1GB00 SIRIUS 3RQ1 Force-Guided Coupling Relay
Fabricator: Siemens
Condición: Nuevo
Plazo de Entrega: En Stock
Origo: Germania
Garantía: 12 Meses
Inscriptio electronica: [email protected]
whatsapp: +86-18150117685
- Conspectus
- Hot Selling Models
- Producta commendata
Conspectus
- Utere relais in applicatione suae interrutionis secundum normas de securitate et in circuitu securo apto.
- Includere experimenta necessaria de vita servitii propter usum et tempus missionis secundum normas de securitate (20 annos).
- Protegere circuitus contactuum NO et NC cum suis diversis certificatis valoribus fusibilium gL/gG.
- Utere longitudinem decorticandae conductoris 10 mm et constringe terminales vitreae ad momentem torque 0.6–0.8 N·m.
3RQ1000-1GB00 SIRIUS 3RQ1 Force-Guided Coupling Relay
A monostable 24 V DC coupling relay with two NO contacts, one NC contact and capability up to SIL 2 / PL c.
Ad Primum Aspectum
| Nota | Siemens |
|---|---|
| Modellum | 3RQ1000-1GB00 |
| Typus Producti | Coupling relay |
| Functio principalis | Transferring control signals through relay contacts |
| Applicatio | Safety-related shutdown interfaces |
Couple control commands
The monostable relay uses two normally open contacts and one normally closed contact.
Support safety-related shutdown
The force-guided contacts comply with IEC 60947-5-1 and the defined safe state is shutdown.
Install in compact panels
A 17.5 mm wide housing supports 35 mm DIN-rail or screw mounting and the 3ZY12 device connector.
Product Overview
3RQ1000-1GB00 provides force-guided relay contacts for safety-related switching-off applications.
The industrial enclosure includes an LED and removable screw terminals, with the component rated for use up to SIL 2 and PL c under the applicable safety configuration.
Key Functions
Couple control commands
The monostable relay uses two normally open contacts and one normally closed contact.
Support safety-related shutdown
The force-guided contacts comply with IEC 60947-5-1 and the defined safe state is shutdown.
Install in compact panels
A 17.5 mm wide housing supports 35 mm DIN-rail or screw mounting and the 3ZY12 device connector.
Official Specifications
| Control Supply | 24 V DC; operating factor 0.8–1.2 |
|---|---|
| Consumptio potestatis activa | 0.9 W |
| Disposizione dei contatti | 2 NO and 1 NC; monostable operation |
| Material Contactus | AgNi with gold flash |
| Maxima currentis thermicae per contactus | 5 A |
| Currente Minime de Exito | 1 mA |
| Classis contactuum AC-15 | 2 A ad 250 V AC |
| Classis contactuum DC-13 | 2 A ad 24 V DC; 0.2 A ad 125 V DC; 0.1 A ad 250 V DC |
| Maximae Dilatationes de Operatione et de Liberatione | 15 ms in retardatione de activatione; 35 ms in retardatione de disactivatione |
| Frequentia Maxima Commutandi | 360 operationes per hora |
| Fusibiles de Contactu Requirite | Contactus NO: 6 A gL/gG; contactus NC: 4 A gL/gG |
| Tensiones Nominales de Insulatione e de Impulsu | 300 V ad categoria de supra-tensio III, gradus de pollutione 3; 4 kV resistentia ad impulsus |
| Capacitas Securitatis | SIL 2; PL c; categoria 1 |
| PFHD | 6 × 10⁻⁷ pro hora |
| Tempus Missionis Securitatis | 20 annis |
| Mecanicus Patiens | 10 milioane de cicluri de funcționare tipice |
| Conexus terminalis | Terminalia vitarum removibilia; longitudo decorticandi 10 mm |
| Par de torsion pro terminalibus | 0,6–0,8 N·m |
| Temperatura operativa | −25 usque ad +60 °C |
| Dimensiones et pondus netum | 17,5 × 100 × 120 mm; 0,142 kg |
Quaestiones Frequenter Rogatae
Num 3RQ1000-1GB00 ad functionem incipientem ad securitatem pertinentem uti potest?
Relais aptum est ad interrumpendum ad securitatem pertinentem, sed non ad inchoandum ad securitatem pertinentem.
Quae dispositio contactuum 3RQ1000-1GB00 ad interfaciem claudendi praebet?
Relais habet duo contacta aperta normaliter ductu viro et unum contactum clausum normaliter ductu viro.
Quale capacità di sicurezza può supportare il circuito appropriato con 3RQ1000-1GB00?
Il componente è classificato fino a SIL 2 e PL c con categoria 1.
È necessario includere il test di usura dei contatti nell’applicazione di 3RQ1000-1GB00?
Per questo relè è richiesto il test della durata operativa correlato all’usura.
I circuiti NA e NC di 3RQ1000-1GB00 devono utilizzare la stessa dimensione di fusibile?
Il fusibile gL/gG richiesto è da 6 A per i contatti NA e da 4 A per il contatto NC.
È possibile alimentare 3RQ1000-1GB00 tramite un connettore per dispositivi 3ZY12?
Il relè supporta il funzionamento con il connettore per dispositivi 3ZY12.
Quanto tempo impiega 3RQ1000-1GB00 a rilasciare dopo la rimozione del segnale di comando?
Il ritardo massimo in spegnimento specificato è di 35 ms.