Overview
- Confirm the AC supply and sink-input wiring of the -001 version before reconnecting field circuits.
- Size external output protection and suppress inductive loads in accordance with the hardware instructions.
- Check both individual relay-contact current and shared-common current.
- For migration, review input commons, program compatibility and expansion hardware rather than assuming unchanged wiring.
FX2N-128MR-001 MELSEC-F FX2N 128-Point Relay PLC
An AC-powered FX2N controller with 64 sink inputs and 64 relay outputs for machine automation and replacement projects.
At a Glance
| Brand | Mitsubishi Electric |
|---|---|
| Model | FX2N-128MR-001 |
| Product Type | Compact programmable controller |
| Core Function | Machine sequencing with relay outputs |
| Application | Legacy FX2N machine-control installations |
Integrated machine I/O
The main unit provides 128 built-in I/O points divided equally between inputs and outputs.
Relay load switching
Relay outputs accommodate AC or DC loads within the contact and common-terminal ratings.
Modular expansion
The FX2N system supports additional I/O and special-function blocks within its system and supply limits.
Product Overview
FX2N-128MR-001 combines 64 digital inputs and 64 relay outputs in a compact FX2N main unit.
The AC-powered Asian-market version supports existing machine-control wiring, while output contact loading, common-terminal current and expansion power budgets determine the installation limits.
Key Functions
Integrated machine I/O
The main unit provides 128 built-in I/O points divided equally between inputs and outputs.
Relay load switching
Relay outputs accommodate AC or DC loads within the contact and common-terminal ratings.
Modular expansion
The FX2N system supports additional I/O and special-function blocks within its system and supply limits.
Official Specifications
| Built-in digital inputs | 64, sink-input arrangement |
|---|---|
| Built-in digital outputs | 64 relay outputs |
| Nominal supply | 100–240 V AC, 50/60 Hz |
| Supply tolerance | +10% / −15% |
| Relay switched voltage | Up to 240 V AC or 30 V DC for resistive loads |
| Resistive output current | 2 A per output point; 8 A per common |
| Maximum inductive load | 80 VA at 120/240 V AC |
| Minimum low-voltage DC load | At least 2 mA when switching below 24 V DC |
| Approximate relay response | 10 ms OFF-to-ON and 10 ms ON-to-OFF |
| Output circuit isolation | Relay isolation |
| Internal output protection | None; external circuit protection sized to the load |
| Maximum system I/O | 256 points, subject to expansion and power budgets |
| Special-function block capacity | Up to 8 per system |
| Main-unit width | 350 mm |
| Approximate main-unit mass | 1.8 kg |
Frequently Asked Questions
Is FX2N-128MR-001 a DC-powered or AC-powered main unit?
This version uses a nominal 100–240 V AC supply.
How are the built-in I/O points of FX2N-128MR-001 divided?
The main unit has 64 digital inputs and 64 relay outputs.
Can FX2N-128MR-001 switch a 240 V AC resistive load?
The relay contacts permit resistive loads up to 240 V AC within the specified current limits.
Can every output sharing a common on FX2N-128MR-001 carry 2 A simultaneously?
The current through each common must remain within 8 A even when individual points are below 2 A.
Does FX2N-128MR-001 provide internal protection for an overloaded output circuit?
The relay outputs have no internal circuit protection, so external protection must suit the connected load.
How should I allow for relay switching time when using FX2N-128MR-001?
Allow approximately 10 ms for either relay turn-on or turn-off in addition to control-program timing.
Can I add special-function blocks to the system based on FX2N-128MR-001?
Up to eight special-function blocks are supported when the complete I/O and supply budgets remain valid.