Siemens SIMATIC PCS 7 Redundant F-DI MTA Connection Module 6ES7650-1AK11-7XX0
Fabricator: Siemens
Condición: Nuevo
Plazo de Entrega: En Stock
Origo: Germania
Garantía: 12 Meses
Inscriptio electronica: [email protected]
whatsapp: +86-18150117685
- Conspectus
- Product Overview
- Key Functions
- Official Specifications
- Quaestiones Frequenter Rogatae
- Compatibility & Ordering Notes
- Hot Selling Models
- Producta commendata
Conspectus
Siemens • SIMATIC PCS 7
6ES7650-1AK11-7XX0 SIMATIC PCS 7 Redundant F-DI MTA Connection Module
The SIMATIC PCS 7 F-DI MTA is a redundant 12/24-channel 24 V DC marshalling assembly for fail-safe digital-input modules, with protected power distribution and channel indication.
Ad Primum Aspectum
| Nota | Siemens |
|---|---|
| Modellum | 6ES7650-1AK11-7XX0 |
| Typus Producti | Redundant fail-safe digital-input marshalling terminal assembly |
| Functio principalis | Marshals and protects redundant 24 V DC safety input channels |
| Applicatio vel series compatibiles | PCS 7 safety I/O using redundant 6ES7326-1BK02-0AB0 modules |
Identificatio exacta.
Match 6ES7650-1AK11-7XX0 character by character and confirm the complete SIMATIC PCS 7 Redundant F-DI MTA Connection Module designation.
Arrangementum Interfacis
Confirmare ante connexionem substitutionis supplitum installatum, portus, connexiones campestres et accessoria requisa.
Configuration Check
Servare projectum ingenieriae approbatum, parametres rete et data applicationis quae systema installatum utitur.
Product Overview
The SIMATIC PCS 7 F-DI MTA is a redundant 12/24-channel 24 V DC marshalling assembly for fail-safe digital-input modules, with protected power distribution and channel indication.
The assembly connects the specified redundant F-DI module arrangement for high-availability process safety applications. Individual channel protection and a protected module supply localize wiring and power faults. Green indicators show input power, module power and channel power conditions.
Key Functions
Redundant Safety I/O Connection
The assembly connects the specified redundant F-DI module arrangement for high-availability process safety applications.
Protected Channel Distribution
Individual channel protection and a protected module supply localize wiring and power faults.
Visible Power Status
Indicatoria viridia conditiones potentiae intrantis, potentiae moduli et potentiae canalium ostendunt.
Official Specifications
| I/O Capacitas | 12 aut 24 canales digitalis fall-safe |
|---|---|
| Tensio Signali | 24 V DC |
| Modulus F-DI compatibilis | 6ES7326-1BK02-0AB0 |
| Dissipatio Energiae Typica | 3 W |
| Filum magnitudinis intervallum | 24 ad 14 AWG |
| Intervalum dimensionum metricarum fili | 0.205 ad 2.08 mm² |
| Fusus canalium singularium | 0.05 A |
| Fusus potentiae moduli | 2.0 A |
| Indicatores Status | LEDs potentiae intrantis, potentiae moduli et potentiae canalium |
| Color of Indicator | Viridis |
| Temperatura operativa horizontalis | −25 ad 70 °C |
| Temperatura operativa verticalis | −25 ad 60 °C |
| Humiditas relativa | 5 % ad 95 %, non condensans |
| 1oo1 Safety Capability | SIL 2, PL d, Category 3 |
| 1oo2 Safety Capability | SIL 3, PL e, Categoria 4 |
| Proof-Test Interval | 20 annis |
Quaestiones Frequenter Rogatae
Which safety input module is compatible with 6ES7650-1AK11-7XX0?
Use it with the specified 24 V DC fail-safe digital-input module in the engineered redundant arrangement.
How many field channels can 6ES7650-1AK11-7XX0 marshal?
The assembly supports a 12-channel or 24-channel connection arrangement according to the selected wiring design.
Quid significent LED in 6ES7650-1AK11-7XX0?
Indicatores virides praesentiam potentiae ad introitum, potentiae moduli et potentiae canalis ostendunt.
Possuntne duo sensoria redundantia unum canalem in 6ES7650-1AK11-7XX0 communicare?
Non; regulae de connexione publicatae non permittunt duo sensoria redundantia in uno canali.
Quales magnitudines filorum in 6ES7650-1AK11-7XX0 coniungi possunt?
Utere conductores ab 24 usque ad 14 AWG, aut ab 0,205 usque ad 2,08 mm², cum praeparatione approbata.
Quid ante substitutionem 6ES7650-1AK11-7XX0 documentandum est?
Registra omnem terminalem, fusibilem canalis, alimentationem potentiae, attributionem moduli redundantis et resultatum experimenti circuitus tutelaris.
Quomodo 6ES7650-1AK11-7XX0 post installationem conprobare debet?
Perage experimentum probationis approbatum et verifica indicationem potentiae, status canalis, diagnosticos et omnem responsionem tutelarem.
Compatibility & Ordering Notes
Index Compatibilitatis
- Utere tantum cum modulo digitalis input fail-safe specificato et cum connexione redundante approbata.
- Observa prohibitionem duorum sensorum redundantium in eodem canalibus.
- Completa examen probatorium de securitate validatum antequam anulum restituas ad usum.