Siemens 6ES7193-6BP00-0DA0 SIMATIC ET 200SP BU15-P16+A0+2D BaseUnit
Fabricator: Siemens
Condición: Nuevo
Plazo de Entrega: En Stock
Origo: Germania
Garantía: 12 Meses
Inscriptio electronica: [email protected]
whatsapp: +86-18150117685
- Conspectus
- Hot Selling Models
- Producta commendata
Conspectus
- Use an ET 200SP I/O module approved for BU type A0.
- Select the light-colored new-group arrangement in the station configuration.
- Provide the separate 24 V DC feed and B- or C-characteristic supply protection.
- Keep the 10 A bus and 2 A process-terminal limits distinct.
- Add the optional shield connection only where the installation requires it.
- Apply the temperature and altitude restrictions for the actual mounting location.
6ES7193-6BP00-0DA0 SIMATIC ET 200SP BU15-P16+A0+2D BaseUnit
A light-colored A0 BaseUnit with 16 push-in process terminals, two supply-bus connections, and an integrated filter for a separately supplied ET 200SP load group.
Ad Primum Aspectum
| Nota | Siemens |
|---|---|
| Modellum | 6ES7193-6BP00-0DA0 |
| Typus Producti | A0 BaseUnit |
| Functio principalis | Starts a new station load group |
| Applicatio | Compatible ET 200SP I/O modules |
Separate load-group supply
The light-colored base opens a new potential group.
Direct process wiring
Sixteen push-in process terminals connect the I/O module.
Nulla fila auxiliaris
Haec versio compacta non habet terminales AUX aut add-on.
Product Overview
6ES7193-6BP00-0DA0 formet novum gruppus oneris ET 200SP utendo dispositione terminalium BU15-P16+A0+2D.
Eius filtrum integratum, separata suppletio potentialis-gruppi et optio connexio scuti permittunt compactam positionem 15 mm pro connexionibus sine addita fila terminalium auxiliarium.
Key Functions
Separare proximum gruppus potentialis
Unitas Basalis incipit novum gruppus potius quam pontificare suppletionem a gruppo ad sinistram suam.
Connecte signa I/O et suppletionem
Decem-sex terminalia processus et duae connexiones suppletionis P1/P2 praebent puncta connexionis moduli.
Integrare filtrationem suppletionis
Filtrum integratum includitur, et connectio scuti integrata in systema addi potest ut optio.
Official Specifications
| Tensio nominalis supplicii | 24 V DC |
|---|---|
| Dispositio Terminalis Processus | 16 terminales ad inserendum; nullae terminales AUX aut add-on |
| Connexiones Bus Alimentationis | Duo terminalia connectuntur ad P1 et P2 |
| Maxima Currentia Bus P1/P2 | 10 A |
| Maximum Process-Terminal Current | 2 A |
| Protectio Lineae Supplicationis | interruptor circuitus minimus 24 V DC, 10 A cum characteristicis B vel C |
| Insulation Type-Test Voltage | 707 V DC |
| Sectio Transversa Conductoris | 0,14–2,5 mm² (AWG 26–14) |
| Temperatura operativa horizontalis | −30 to +60 °C |
| Temperatura operativa verticalis | −30 to +50 °C |
| Altitudo Installationis Maxima | 5 000 m; restrictiones valent supra 2 000 m |
| Minimum Dew Point | −60 °C, pro applicationibus in camera arida |
| Etiquettae Colorum Terminalium Processus | CC00–CC09 |
| Dimensionum totalium | 15 × 117 × 35 mm (latitudo × altitudo × profunditas) |
| Pondus Approximatum | 40 g |
Quaestiones Frequenter Rogatae
Utrum 6ES7193-6BP00-0DA0 utendum est ut gruppus oneris ad sinistram continuetur?
Haec Unitas Basi clara novum gruppus potentialis incipit, non autem gruppus ad sinistram continuat.
Can I land additional AUX wires on 6ES7193-6BP00-0DA0?
The base has neither AUX terminals nor add-on terminals.
How do I protect the supply lines feeding 6ES7193-6BP00-0DA0?
Use a 24 V DC, 10 A miniature circuit breaker with a B or C tripping characteristic.
What is the difference between the bus and process limits on 6ES7193-6BP00-0DA0?
The P1/P2 buses carry up to 10 A, while each process terminal is limited to 2 A.
Can I add a shield connection to 6ES7193-6BP00-0DA0?
Coniunctio scuti integrata in systemate disponibilis est ut optio.
Which conductor range fits the push-in terminals of 6ES7193-6BP00-0DA0?
The terminals accept 0.14–2.5 mm² conductors, corresponding to AWG 26–14.
What temperature limit changes when I mount 6ES7193-6BP00-0DA0 vertically?
The operating range is −30 to +50 °C vertically compared with −30 to +60 °C horizontally.