- Overview
- Specifications
- Description
- Applications
- Installation in Hazardous Locations
- Preinstallation Check
- Configuration Parameters
- FAQ
- Recommended Products
Overview
Place of Origin: |
USA |
Brand Name: |
GE |
Model Number: |
IC200MDD843 |
Packaging Details: |
Original new Factory Sealed |
Delivery Time: |
5-7 days |
Payment Terms: |
T/T |
Supply Ability: |
In stock |
Specifications
|
Model: |
IC200MDD843 |
|
Module Type: |
Discrete Input/Output Module |
|
I/O Points: |
10 DC inputs (one group); 6 Form A relay outputs (one group) |
|
Isolation: |
Input to logic/frame ground: 250 VAC continuous, 1500 VAC 1 min; Group-to-group: same; Point-to-point: N/A |
|
LED Indicators: |
One LED per point (ON/OFF); OK LED (backplane power) |
|
External Power Supply: |
0–125 VDC (5/24/125 VDC nominal); 0–265 VAC, 47–63 Hz (120/240 VAC nominal) |
|
Thermal Derating: |
None |
|
Input Voltage: |
0–30 VDC (24 VDC nominal) |
|
On-State Voltage: |
15–30 VDC |
|
Off-State Voltage: |
0–5 VDC |
|
On-State Current: |
2.0–5.5 mA |
|
Off-State Current: |
0–0.5 mA |
|
Input Response Time: |
0.5 ms max |
|
Configurable Filter Time: |
0 ms, 1 ms (default), 7 ms |
|
Input Impedance: |
10 kΩ max |
|
Output Voltage: |
0–125 VDC or 0–265 VAC (120/240 VAC nominal) |
|
Output Voltage Drop: |
0.3 V max |
|
Load Current: |
10 mA min per point; up to 2 A (5–265 VAC), 2 A (5–30 VDC), 0.2 A (31–125 VDC); 8 A max per module/group |
|
Output Leakage Current: |
Not applicable (open contact) |
|
Output Response Time: |
10 ms max |
|
Protection: |
No internal fuses or snubbers |
|
Switching Frequency: |
20 cycles/min (inductive load) |
|
Relay Type: |
Fixed coil, moving armature |
|
Contact Type: |
Silver alloy |
Description
Discrete input/output module IC200MDD843 provides 10 discrete inputs and 6 relay outputs. The inputs form one group of 10 points. Inputs are positive logic or sourcing-type inputs; they receive current from devices and return the current on the common. The relay outputs form two groups of 6 points. Each output group can drive a maximum of 8 Amps. Power for module operation comes from the backplane. Output loads must be powered by an external source. Intelligent processing for the module is performed by the CPU or NIU.
Applications
Assembly and packaging plants: Used to detect product arrival (input) and directly start sealing machines or push rods (output).
Food and beverage processing plants: Control small pumps, mixers, or conveyor belt sorting mechanisms.
Textile and garment plants: Suitable for logic control of small automated sewing equipment or fabric cutting tables.
Electronic component manufacturing plants: Serves as a core control unit in precision components or small inspection tables, saving cabinet space.
Installation in Hazardous Locations
1 Equipment labeled with reference to Class I, Groups A, B, C & D, Div. 2 hazardous locations is suitable for use in Class I, Division 2, Groups A, B, C, D or non-hazardous locations only
2 Warning - Explosion hazard - substitution of components may impair suitability for Class I, Division 2
3 Warning - Explosion hazard - when in hazardous locations, turn off power before replacing or wiring modules
4 Warning - Explosion hazard - do not disconnect equipment unless power has been switched off or the area is known to be nonhazardous
Preinstallation Check
Carefully inspect all shipping containers for damage. If any equipment is damaged, notify the delivery service immediately. Save the damaged shipping container for inspection by the delivery service. After unpacking the equipment, record all serial numbers. Save the shipping containers and packing material in case it is necessary to transport or ship any part of the system.
Configuration Parameters
The module’s basic input on/off response time is 0.5ms. For some applications, it may be preferable to add additional filtering to compensate for conditions such as noise spikes or switch bounce. Input filter times of 0ms, 1.0ms, or 7.0ms are selectable via software configuration for total response times of 0.5ms, 1.5ms, and 7.5ms respectively. The default is 1.0ms filter time (total response time is 1.5ms).
FAQ
Q: What is the IC200MDD843?
A: It is a Discrete input/output module.
Q: What shipping methods are used for IC200MDD843?
A: Major carriers like FedEx, DHL, and UPS are primarily used for worldwide delivery.