Overview
Place of Origin: |
USA |
Brand Name: |
Bently Nevada |
Model Number: |
3300/35 |
Packaging Details: |
Original new Factory Sealed |
Delivery Time: |
5-7 days |
Payment Terms: |
T/T |
Supply Ability: |
In stock |
Quick Detail
|
Product Name |
3300/35 Six-Channel RTD Monitor |
|
Function |
Six independent channels of on-line temperature monitoring; accepts up to six RTD signals |
|
RTD Types and Ranges |
3-wire 100 Ω platinum (α = 0.00385) 500°C/1000°F; 3-wire 100 Ω platinum (α = 0.00392) 500°C/1000°F; 3-wire 120 Ω nickel 150°C/300°F; 3-wire 10 Ω copper 100°C/200°F; 4-wire 100 Ω platinum (α = 0.00385) 500°C/1000°F; 4-wire 100 Ω platinum (α = 0.00392) 500°C/1000°F; 4-wire 120 Ω nickel 150°C/300°F; 4-wire 10 Ω copper 100°C/200°F; changing between platinum/nickel and copper RTD requires monitor recalibration via plug-in jumpers |
|
Power Consumption |
Nominal 4 W |
|
Monitor Range |
Full-scale operating range user-selected; factory calibrated; field reprogrammable for recorder/computer interface proportional signals |
|
Display Accuracy |
±1°C (1.8°F) with tenths digit; ±1.5°C (2.7°F) without tenths digit at +25°C (+77°F) |
|
Output Impedance (Voltage Outputs) |
100 Ω; minimum load resistance 10 kΩ |
|
Voltage Compliance (Current Outputs) |
0 to +12 Vdc; load resistance 0–600 Ω with +4 to +20 mA option |
|
Dimension: |
5.1 cm x 20.3 cm x 33.0 cm |
|
Weight: |
1.5 kg |
Description
The 3300/35 Six-Channel Temperature RTD Input Monitor provides six independent channels for on-line temperature monitoring in automated industrial systems. The 3300/35 Six-Channel Temperature RTD Input Monitor accepts up to six RTD signals, including 3-wire and 4-wire 100 Ω platinum (α = 0.00385 or 0.00392) up to 500°C/1000°F, 120 Ω nickel up to 150°C/300°F, and 10 Ω copper up to 100°C/200°F, with field recalibration via plug-in jumpers when changing RTD types.
The 3300/35 Six-Channel Temperature RTD Input Monitor features digitally adjustable Alarm 1 and Alarm 2 per channel from 0–500°C (0–1000°F) with ±1°C repeatability, a 7-segment 4-digit LCD displaying channel readings, alarm status, and error codes, and LED indicators for OK, Alarm, and Bypass. Voltage outputs are 0–+12 Vdc, and current outputs +4 to +20 mA across 0–600 Ω, with 100 Ω output impedance. Full-scale ranges are user-selected and factory-calibrated, with field reprogramming for recorder or computer interface. Operating temperature is 0°C to +65°C, storage -40°C to +85°C, and nominal power consumption is 4 W. The 3300/35 Six-Channel Temperature RTD Input Monitor supports automated temperature monitoring in turbines, compressors, and industrial machinery control systems.
Applications
Monitor turbine and compressor temperatures
The 3300/35 Six-Channel Temperature RTD Input Monitor measures six independent RTD channels, providing accurate readings up to 500°C (1000°F) with ±1°C repeatability, enabling automated detection of overheating points.
Trigger automated high/low temperature alarms
Using digitally adjustable Alarm 1 and Alarm 2 per channel, the 3300/35 Six-Channel Temperature RTD Input Monitor sends real-time alarm outputs to PLCs or DCS systems, supporting automated shutdown or protective actions.
Transmit temperature data to control and logging systems
The 3300/35 Six-Channel Temperature RTD Input Monitor provides voltage outputs (0–+12 Vdc) and current outputs (+4 to +20 mA) with 100 Ω impedance, integrating RTD measurements directly into automated monitoring systems.
Isolate channels for maintenance without disrupting others
LED indicators for OK, Alarm, and Bypass on the 3300/35 Six-Channel Temperature RTD Input Monitor allow operators to bypass individual channels or view error codes while maintaining continuous monitoring on other channels.
Specifications
|
Alarm Setpoints |
Alarm 1 and Alarm 2 per channel digitally adjustable 0–500°C (0–1000°F); 1 digit resolution; repeatable ±1°C (1.8°F); Alarm 1 over-alarm; Alarm 2 user-programmable over/under |
|
Relay Module Location |
One alarm relay module can be installed behind each monitor; at least one relay module required per 3300 System |
|
LED Indicators OK |
One constant green LED per monitor indicates OK condition of all six transducers; OFF = one or more channels NOT OK; flashing 5 Hz = error codes stored |
|
LED Indicators Alarm |
Two LEDs indicate Alarm 1 and Alarm 2 status; flashing = rack First Out |
|
LED Indicators Bypass |
Red LED indicates status of Alarm 2 Bypass and Rack/Channel Bypass functions |
|
Operating Temperature |
0°C to +65°C (+32°F to +150°F) |
|
Storage Temperature |
-40°C to +85°C (-40°F to +185°F) |
|
Relative Humidity |
Up to 95%, non-condensing |
Competitive Advantage
Six independent RTD channels in one module
The 3300/35 Six-Channel Temperature RTD Input Monitor consolidates six RTD inputs, reducing rack space and wiring while supporting multiple measurement points.
High-resolution display with repeatable digital alarms
With ±1°C accuracy, 0.1-unit LCD resolution, and repeatable Alarm 1 and Alarm 2 setpoints, the 3300/35 Six-Channel Temperature RTD Input Monitor provides precise temperature monitoring for critical machinery.
Flexible output for automation integration
The 3300/35 Six-Channel Temperature RTD Input Monitor outputs voltage or current signals with 100 Ω impedance, allowing direct connection to PLCs, DCS, or recording devices for automated control.
Low-power operation for dense automation racks
With only 4 W nominal power consumption, the 3300/35 Six-Channel Temperature RTD Input Monitor allows multiple units to operate in a single rack without exceeding power limits, supporting continuous automated temperature monitoring.