Siemens SIWAREX WP231 7MH4960-2AA01 S7-1200 Weighing Module
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Confirm the load-cell type, bridge resistance, total capacity and 1 to 4 mV/V characteristic.
- Select four-wire or six-wire connection and maintain the approved shielding arrangement.
- Choose either S7-1200 integration or stand-alone operation before commissioning.
- Verify Ethernet, RS485 and local I/O assignments.
- For legal-for-trade use, confirm the approved display, sealing, calibration and national regulations.
- Use the specified RS485 arrangement when adding a SIWAREX DB digital junction box.
Siemens · SIWAREX WP231
7MH4960-2AA01 Single-Channel Weighing Module
Siemens 7MH4960-2AA01 SIWAREX WP231 is compact single-channel weighing electronics for analog full-bridge load cells, operating as a SIMATIC S7-1200 expansion module or as a stand-alone controller.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 7MH4960-2AA01 |
| Product Type | Single-Channel Legal-for-Trade Weighing Electronics |
| Core Function | Processes one analog full-bridge load-cell signal for non-automatic weighing |
| Application or Compatible Series | SIMATIC S7-1200 or stand-alone platform, hopper, silo and crane scales |
Flexible Operating Architecture
Select either SIMATIC S7-1200 integration or stand-alone operation before assigning communication and I/O.
Scale Electrical Match
Verify the 1 to 4 mV/V full-bridge characteristic, resistance, capacity and four-wire or six-wire topology.
Verification Planning
For legal-for-trade use, include the approved display, sealing, calibration and country-specific metrology requirements.
Product Overview
Siemens 7MH4960-2AA01 SIWAREX WP231 is compact single-channel weighing electronics for analog full-bridge load cells, operating as a SIMATIC S7-1200 expansion module or as a stand-alone controller.
The module acquires one four-wire or six-wire full-bridge circuit and converts it into a stable weight value. Parameterizable digital I/O and a current output provide switching, limit and process-value functions. Ethernet, RS485 and SIWATOOL support setup, while a compatible SIWAREX DB junction box adds detailed load-cell diagnostics.
Key Functions
Load-Cell Signal Processing
The module acquires one four-wire or six-wire full-bridge circuit and converts it into a stable weight value.
Local Scale Control
Parameterizable digital I/O and a current output provide switching, limit and process-value functions.
Commissioning and Diagnostics
Ethernet, RS485 and SIWATOOL support setup, while a compatible SIWAREX DB junction box adds detailed load-cell diagnostics.
Official Specifications
| Rated Supply Voltage | 24 V DC |
|---|---|
| Permissible Supply Range | 19.2 to 28.8 V DC |
| Maximum Current Consumption | 200 mA |
| Typical 5 V Backplane Current | 3 mA |
| Typical Power Loss | 4.5 W |
| Load-Cell Signal Range | 1 to 4 mV/V |
| Load-Cell Wiring | Four-wire or six-wire full bridge |
| Full-Bridge Resistance | 40 to 4100 Ω without an optional SIWAREX IS interface |
| Internal Weighing Resolution | Up to ±4 million parts |
| Digital Inputs | 4, parameterizable |
| Digital Outputs | 4, short-circuit protected |
| Digital Output Capacity | 0.5 A per channel; 4 A maximum per module |
| Digital Output Delay | 25 µs maximum on; 150 µs maximum off |
| Analog Output | One channel, 0 to 20 mA or 4 to 20 mA |
| Analog Output Resolution | 16 bits including sign |
| Analog Output Load | 600 Ω maximum |
| RS485 Interface | One interface, up to 115.2 kbit/s and 1000 m with suitable shielded cable |
| Ethernet Interface | One RJ45 port |
| Diagnostics | Supply-voltage, wire-break and short-circuit monitoring |
| Dimensions | 70 × 100 × 75 mm |
Frequently Asked Questions
Which load cells can be connected to 7MH4960-2AA01?
Use analog strain-gauge full bridges with a 1 to 4 mV/V characteristic and either a four-wire or six-wire connection.
Can 7MH4960-2AA01 operate without an S7-1200 CPU?
The weighing electronics can run in stand-alone mode through its integrated communication and I/O interfaces.
Which local I/O is available on 7MH4960-2AA01?
The unit provides four parameterizable digital inputs, four protected digital outputs and one analog current output.
Which communication interfaces are built into 7MH4960-2AA01?
One RJ45 Ethernet interface and one RS485 interface are integrated.
Can 7MH4960-2AA01 be used for legal-for-trade weighing?
It is designed for non-automatic legal-for-trade scales when the complete installation satisfies local approval and verification rules.
How can enhanced load-cell diagnostics be added to 7MH4960-2AA01?
Connect a compatible SIWAREX DB digital junction box using the specified RS485 arrangement.
What should be checked before commissioning 7MH4960-2AA01?
Verify the bridge resistance, mV/V rating, wiring method, scale calibration, I/O assignments, supply and local metrology requirements.