Siemens 6ES7132-6BH01-0BA0 ET 200SP DQ 16x24VDC/0.5A ST Output Module
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Use CC00 terminal identification and the appropriate A0 BaseUnit.
- Apply the horizontal or vertical derating limits to the module total.
- Allow the optional two QI bytes in the station configuration.
- Use module-level fault diagnostics and separate channel-status indicators appropriately.
6ES7132-6BH01-0BA0 ET 200SP DQ 16x24VDC/0.5A ST Output Module
The 16-channel standard output module provides PNP sourcing outputs, module-level diagnostics and optional quality information in a 15 mm wide ET 200SP housing.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7132-6BH01-0BA0 |
| Product Type | Digital output module |
| Core Function | Switching of DC field loads |
| Application | ET 200SP distributed I/O stations |
16 sourcing outputs
Each PNP channel switches up to 0.5 A at 24 V DC.
Module diagnostics
Supply, wire-break and short-circuit diagnostics operate at module level.
BaseUnit A0
CC00 color coding identifies the module-specific terminal assignment.
Product Overview
6ES7132-6BH01-0BA0 is an ET 200SP standard digital output module with 16 current-sourcing channels. It combines electronic short-circuit protection with module diagnostics for supply faults, wire break and short circuits to L+ or ground.
The module uses two output bytes, with two additional bytes for quality information, and fits BaseUnit type A0 with the CC00 module color code.
Key Functions
PNP load switching
Sixteen sourcing outputs provide 0.5 A per channel for suitable 24 V DC loads, with electronic short-circuit protection.
Quality and fault visibility
Optional QI bytes accompany the output data, while the module provides green channel-status LEDs and a green/red DIAG indicator.
Temperature-dependent load capacity
The permitted aggregate current changes with ambient temperature and horizontal or vertical mounting.
Official Specifications
| Output channels | 16 PNP current-sourcing outputs |
|---|---|
| Supply voltage | 24 V DC nominal; permissible 19.2 to 28.8 V |
| Maximum no-load current | 30 mA |
| Typical power loss | 1 W |
| Process-data allocation | 2 output bytes plus 2 bytes for QI information |
| Rated current per output | 0.5 A |
| Horizontal mounting total current | 8 A up to 40 °C; 6 A up to 50 °C; 4 A up to 60 °C |
| Vertical mounting total current | 8 A up to 30 °C; 6 A up to 40 °C; 4 A up to 50 °C |
| Short-circuit response threshold | Typically 1 A; range 0.7 to 1.3 A |
| Load resistance | 48 Ω to 12 kΩ |
| Maximum lamp load | 5 W |
| Maximum OFF residual current | 0.1 mA |
| Typical output delay | 50 µs ON; 100 µs OFF |
| Maximum resistive and lamp switching rates | 100 Hz resistive; 10 Hz lamp loads |
| Maximum output cable length | 1000 m shielded; 600 m unshielded |
| Isolation test voltage | 707 V DC, type test |
| Dimensions (W × H × D) | 15 × 73 × 58 mm |
| Approximate weight | 30 g |
Frequently Asked Questions
Which BaseUnit should I select for two-wire loads on 6ES7132-6BH01-0BA0?
Two-wire wiring uses a type A0 BaseUnit with AUX terminals or a potential distributor module.
Can I run all sixteen outputs on 6ES7132-6BH01-0BA0 at 0.5 A with horizontal mounting at 60 °C?
At 60 °C the horizontal-mounting limit is 4 A for the whole module.
Will 6ES7132-6BH01-0BA0 identify the exact channel causing a wire-break diagnostic?
Wire-break diagnostics are module-wide rather than channel-specific.
Can I parallel two outputs of 6ES7132-6BH01-0BA0 to obtain more load current?
Parallel operation is permitted for redundant control of a load but not for increasing its current capacity.
What extra process data does QI add to 6ES7132-6BH01-0BA0?
Quality information adds two bytes to the two-byte output process-data allocation.
Can I use 6ES7132-6BH01-0BA0 with current-sinking output wiring?
The output stage sources current through PNP switching and does not provide current-sinking outputs.
Which TIA Portal versions can configure 6ES7132-6BH01-0BA0?
Configuration is available in TIA Portal V14 with HSP0222 and is integrated from TIA Portal V15.