- Use the source-input, m-reading circuit with L+ as its signal reference.
- Choose the A0 BaseUnit for one- or two-wire wiring and an AUX-equipped A0 base for three-wire sensors.
- Provide external terminals for the documented four-wire connection arrangement.
- Select the input-delay value for the field signal and cable conditions.
- Use the applicable GSD revision 5 or GSDML V2.3 station description where required.
- Do not rely on pulse extension, hardware interrupts or wire-break diagnostics for this Basic module.
6ES7131-6BF60-0AA0 SIMATIC ET 200SP DI 8x24VDC SRC BA Input Module
An eight-channel Basic source-input module with m-reading inputs, selectable input delays, a one-byte input address area and supply-voltage diagnostics.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7131-6BF60-0AA0 |
| Product Type | Source-input digital module |
| Core Function | Acquiring discrete field-input states |
| Application | ET 200SP stations with BaseUnit type A0 |
Source-input wiring
Signal thresholds are referenced to L+, with m-reading field inputs.
BaseUnit selection
One- and two-wire connections use A0 bases; three-wire wiring uses an A0 base with AUX terminals.
Configurable delay
Eight delay selections allow the input response to suit the field wiring.
Product Overview
6ES7131-6BF60-0AA0 acquires eight discrete source-input signals in an ET 200SP station using the A0 BaseUnit interface.
The module provides a one-byte input process area, parameterizable standard-input delays and module diagnostics, with CC02 color identification for the field connections.
Key Functions
Read the source-input signal levels
The m-reading input stage uses a signal-1 threshold of −11 to −30 V relative to L+ and supports IEC 61131 Type 1 and Type 3 input characteristics.
Set the standard-input delay
The configurable delay choices span 0.05 to 20 ms, with additional propagation delay dependent on line length.
Monitor supply and module status
Supply monitoring, readable diagnostic information, green channel LEDs and the green/red DIAG indicator support station commissioning and fault checks.
Official Specifications
| Digital Input Count | 8 |
|---|---|
| Load Supply | 24 V DC nominal; 19.2–28.8 V DC permissible range |
| Input Characteristic | Source input, m-reading; IEC 61131 Type 1 and Type 3 |
| Input Signal Thresholds Relative to L+ | Signal 0: +30 to −5 V; signal 1: −11 to −30 V |
| Typical Signal-1 Input Current | 6 mA |
| Configurable Standard-Input Delays | 0.05, 0.1, 0.4, 0.8, 1.6, 3.2, 12.8 or 20 ms, plus 30–500 µs depending on line length |
| Maximum Two-Wire Sensor Quiescent Current | 1.5 mA |
| Input Address Space | 1 byte |
| Maximum Signal-Cable Length | 1000 m shielded; 200 m unshielded |
| Typical Power Loss | 1.5 W |
| Isolation Test Voltage | 707 V DC, type test |
| Channel Isolation Arrangement | Channels isolated from backplane; no channel-to-channel isolation |
| Firmware | V1.0; firmware update supported |
| Identification and Maintenance Data | I&M0 to I&M3 |
| Module-Specific Color Code | CC02 |
| Status Indicators | Green PWR and channel LEDs; green/red DIAG LED |
| Dimensions (Width × Height × Depth) | 15 × 73 × 58 mm |
| Approximate Weight | 28 g |
Frequently Asked Questions
Which reference potential should I use when checking the inputs of 6ES7131-6BF60-0AA0?
Measure the input signal levels relative to L+ because the module uses m-reading source inputs.
Which base do I need for three-wire sensors on 6ES7131-6BF60-0AA0?
Use a type A0 BaseUnit with AUX terminals for three-wire connections.
How much input process-image space does 6ES7131-6BF60-0AA0 occupy?
The module occupies one byte of input address space.
Can 6ES7131-6BF60-0AA0 extend a brief input pulse?
The module does not provide pulse extension.
How far may I run an unshielded input cable to 6ES7131-6BF60-0AA0?
The maximum unshielded signal-cable length is 200 m.
Will 6ES7131-6BF60-0AA0 report a broken sensor wire as a channel diagnostic?
The module does not provide wire-break or channel-specific diagnostic indications.
Which STEP 7 versions can configure 6ES7131-6BF60-0AA0?
The module can be configured with TIA Portal V13 or STEP 7 V5.5 SP3 and the applicable hardware support.