Siemens 6ES7121-1BB00-0AA0 SIMATIC SC Two-Channel 24V Digital Input Module
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Use the compatible TB16SC or TB16IM-SC Smart Connect arrangement.
- Keep sensor signals within the stated input ranges and account for the 1.2 to 4.8 ms delay.
- Observe the two-wire sensor current limit and cable-length limits.
- Do not assume isolation or diagnostic functions that this submodule does not provide.
6ES7121-1BB00-0AA0 SIMATIC SC Two-Channel 24V Digital Input Module
A single-width two-input Smart Connect module for 24 V DC field signals on the TB16SC terminal system.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7121-1BB00-0AA0 |
| Product Type | Digital input electronic submodule |
| Core Function | Acquire discrete sensor signals |
| Application | ET 200L-SC and ET 200L-SC IM-SC stations |
Two input channels
Both channels can be used simultaneously at the rated 24 V DC signal level.
Compact SC footprint
The 10 mm-wide module uses one terminal-block position.
Visible input state
A green LED indicates the state of each input.
Product Overview
6ES7121-1BB00-0AA0 provides two digital inputs in the SIMATIC Smart Connect electronic-module arrangement.
The 2DI DC24V submodule uses IEC 1131 Type 1 input characteristics and accepts suitable two-wire proximity switches. The two input transitions each have a delay of 1.2 to 4.8 ms.
Key Functions
Read 24 V sensor signals
Signal 1 is detected from 13 to 30 V, while signal 0 covers −3 to +5 V.
Connect proximity switches
Two-wire BEROs are permitted when their closed-circuit current is no more than 1.5 mA.
Indicate channel state
The front provides a green status LED for each input, visible through the labeling strip.
Official Specifications
| Digital Inputs | 2, simultaneously usable |
|---|---|
| Rated Input Voltage | 24 V DC |
| Signal-1 Voltage Range | 13 to 30 V |
| Signal-0 Voltage Range | −3 to +5 V |
| Typical Signal-1 Input Current | 7 mA |
| Input Delay in Either Direction | 1.2 to 4.8 ms |
| Input Characteristic | IEC 1131, Type 1 |
| Maximum Sensor Closed-Circuit Current | 1.5 mA for two-wire BEROs |
| Maximum Field Cable Length | 600 m unshielded; 1,000 m shielded |
| Insertion Cycles into TB16SC | 20 maximum |
| Channel and SC-Bus Isolation | No galvanic isolation between channels or between channels and SC bus |
| Permissible Circuit Potential Difference | 75 V DC or 60 V AC |
| Typical Power Loss | 0.4 W |
| Channel Indication | One green LED per input |
| Interrupts and Diagnostic Functions | Not provided |
| Dimensions (W × H × D) | 10 × 64 × 51 mm |
| Approximate Weight | 15 g |
Frequently Asked Questions
Can I use both channels of 6ES7121-1BB00-0AA0 at the same time?
Yes, both digital inputs can be controlled simultaneously.
What sensor voltage produces signal 1 on 6ES7121-1BB00-0AA0?
An input voltage from 13 to 30 V is within the signal-1 range.
Can a two-wire BERO be connected to 6ES7121-1BB00-0AA0?
Yes, a two-wire BERO is suitable when its closed-circuit current does not exceed 1.5 mA.
How quickly does 6ES7121-1BB00-0AA0 respond to an input transition?
The delay is 1.2 to 4.8 ms for both rising and falling input transitions.
Does 6ES7121-1BB00-0AA0 isolate its channels from the SC bus?
No, the channels are not galvanically isolated from the SC bus or from each other.
Will 6ES7121-1BB00-0AA0 generate diagnostic interrupts for an input fault?
No, the submodule provides neither interrupts nor diagnostic functions.
Can I replace 6ES7121-1BB00-0AA0 repeatedly in the same TB16SC slot?
The permitted number of insertions into a TB16SC slot is 20.