- Set the input-range selector to match the actual mains supply before energizing.
- For two-phase operation, use connected two-pole protection or the specified Siemens circuit-breaker alternative.
- Select constant-current operation or latching shutdown to suit the load response.
- Retain the 50 mm top and bottom clearances for natural convection.
6EP1333-3BA10 SITOP PSU200M 24 V 5 A Power Supply
A 120 W modular SITOP supply with selectable AC input ranges, adjustable 24–28.8 V DC output and a 24 V OK relay contact.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6EP1333-3BA10 |
| Product Type | Stabilized industrial power supply |
| Core Function | Converting AC mains into regulated DC power |
| Application | Control-cabinet DC power distribution |
Adapt to the selected mains range
The input selector provides nominal 120–230 V and 230–500 V AC ranges with their respective permissible voltage windows.
Supply a regulated DC load
The nominal output is 24 V at 5 A and can be adjusted from 24 to 28.8 V with the potentiometer.
Bridge brief supply and load events
Mains buffering is at least 25 ms at 120/230 V and rated load, with a typical 15 A operational short-circuit boost for 25 ms.
Product Overview
6EP1333-3BA10 provides a regulated 24 V DC, 5 A output from a single- or two-phase AC connection. A selector switch chooses the appropriate mains-voltage range.
The supply combines mains buffering with a short-duration output-current boost for transient loads. Two units can operate in parallel to increase capacity, and the selectable protection response can use constant-current operation or latching shutdown.
Key Functions
Adapt to the selected mains range
The input selector provides nominal 120–230 V and 230–500 V AC ranges with their respective permissible voltage windows.
Supply a regulated DC load
The nominal output is 24 V at 5 A and can be adjusted from 24 to 28.8 V with the potentiometer.
Bridge brief supply and load events
Mains buffering is at least 25 ms at 120/230 V and rated load, with a typical 15 A operational short-circuit boost for 25 ms.
Official Specifications
| Nominal selectable AC ranges | 120–230 V or 230–500 V; single- or two-phase connection |
|---|---|
| Permissible AC input windows | 85–264 V in range 1; 176–550 V in range 2 |
| Input frequency | 47–63 Hz |
| Rated input currents | 2.2 A at 120 V; 1.2 A at 230 V; 0.61 A at 500 V |
| Maximum inrush at 25 °C | 35 A |
| Internal input fuse | T 3.15 A, not accessible |
| Mains buffering at rated load | Minimum 25 ms at 120/230 V; typical 150 ms at 400 V |
| Rated DC output | 24 V, 5 A, 120 W |
| Output adjustment range | 24–28.8 V |
| Overall output-voltage tolerance | 3% |
| Maximum output ripple and peaks | 50 mV ripple; 200 mV peaks |
| 24 V OK relay contact | Normally open; 30 V DC / 0.1 A within SELV (ES1) limits |
| Maximum response delay and typical rise time | 1 s delay; 50 ms voltage rise |
| Operational short-circuit boost | 15 A typical for 25 ms |
| Maximum parallel units for increased power | 2 |
| Typical efficiency and power loss | 88%; 17 W at rated output |
| Electrical protection | IP20, Class I; isolated SELV output |
| Operating ambient and cooling | −25 to +70 °C with natural convection |
| Input and output conductor sizes | 0.2–2.5 mm², single-core or finely stranded |
| Enclosure and mounting | 70 × 125 × 121 mm; 0.6 kg; 35 mm EN 60715 DIN rail |
Frequently Asked Questions
Does 6EP1333-3BA10 select its input-voltage range automatically?
The input range is set using the selector switch on the device.
Can I connect 6EP1333-3BA10 between two AC phases?
The supply supports two-phase operation with the required connected two-pole feeder protection.
Can I trim 6EP1333-3BA10 to 28.8 V for a higher-voltage DC bus?
The output potentiometer permits adjustment from 24 to 28.8 V.
Can I parallel two units of 6EP1333-3BA10 for a larger load?
Up to two units can be connected in parallel to increase output capacity.
What relay rating should I allow when wiring the 24 V OK signal from 6EP1333-3BA10?
The normally open signaling contact is rated for 30 V DC at 0.1 A within SELV limits.
Can I mount 6EP1333-3BA10 directly against wiring ducts above and below it?
The enclosure needs 50 mm clearance above and 50 mm below for natural convection.
Can I replace the internal fuse of 6EP1333-3BA10 during routine service?
The internal T 3.15 A fuse is not accessible.