Siemens 3RA2711-1AA00 SIRIUS IO-Link Function Module for Direct Starters
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Use only the compatible communication-capable 3RT20 contactor version and supported size.
- Specify a direct starter rather than a reversing or star-delta assembly.
- Provide 24 V DC and an IO-Link control interface.
- Select conductor sizes for solid or ferruled wiring and maintain the front-mounting arrangement.
3RA2711-1AA00 SIRIUS IO-Link Function Module for Direct Starters
A 24 V DC IO-Link function module for front mounting on compatible communication-capable 3RT20 contactors.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 3RA2711-1AA00 |
| Product Type | Contactor function module |
| Core Function | Linking contactor control to communication |
| Application | Direct-on-line motor starter assemblies |
Communicate through IO-Link
The function module provides a control-circuit interface for IO-Link.
Equip direct starters
The direct-start configuration is intended for contactor sizes S00, S0, S2 and S3.
Simplify contactor assembly
The module plugs onto the front of a compatible contactor and incorporates a varistor suppressor.
Product Overview
3RA2711-1AA00 adds an IO-Link control interface to a compatible SIRIUS direct starter.
The front-mounted module is intended for communication-capable 3RT20 contactors and uses removable screw terminals for the auxiliary and control circuits.
Key Functions
Communicate through IO-Link
The function module provides a control-circuit interface for IO-Link.
Equip direct starters
The direct-start configuration is intended for contactor sizes S00, S0, S2 and S3.
Simplify contactor assembly
The module plugs onto the front of a compatible contactor and incorporates a varistor suppressor.
Official Specifications
| Control Supply | 24 V DC |
|---|---|
| Contactor Sizes | S00, S0, S2 and S3 |
| Control Interface | IO-Link; no AS-Interface connection |
| Starter Configuration | Direct starter; excludes reversing and star-delta arrangements |
| Surge Suppression | Varistor |
| Rated Insulation Voltage | 690 V AC at pollution degree 3 |
| Front Protection | IP20; finger-safe from the front |
| Operating Temperature | −25 to +60 °C |
| Storage and Transport Temperature | −40 to +80 °C |
| Maximum Installation Altitude | 2,000 m |
| Mounting | Plug-in attachment to contactor; any mounting position |
| Terminal Arrangement | Removable screw terminals for auxiliary and control circuits |
| Solid Auxiliary Conductors | 0.5–4 mm²; two conductors each 0.5–2.5 mm² |
| Ferruled Auxiliary Conductors | One conductor 0.5–2.5 mm²; two conductors each 0.5–1.5 mm² |
| Shock Resistance | 11 g for 15 ms |
| Vibration Resistance | 10–55 Hz at 0.35 mm |
| Dimensions (W × H × D) | 45 × 37 × 75 mm |
Frequently Asked Questions
Will 3RA2711-1AA00 fit any 3RT20 contactor?
Use the communication-capable 3RT20…-…..-0CC0 version in size S00, S0, S2 or S3.
Can 3RA2711-1AA00 be used for a reversing starter?
This function module is intended for direct starters and is not suitable for reversing or star-delta starters.
Does 3RA2711-1AA00 connect to an AS-Interface master?
The control interface is IO-Link rather than AS-Interface.
Where is 3RA2711-1AA00 installed on the contactor?
The module plugs onto the front of the compatible contactor.
Which supply should I plan for 3RA2711-1AA00?
The control circuit uses 24 V DC.
Can I unplug the auxiliary terminals of 3RA2711-1AA00 during panel servicing?
The auxiliary and control circuits use removable screw terminals.
What suppressor is built into 3RA2711-1AA00?
The module uses a varistor for surge suppression.