Siemens SIMATIC 6ES7972-0CB35-0XA0 TS Adapter II Modem Analogicum
Fabricator: Siemens
Condición: Nuevo
Plazo de Entrega: En Stock
Origo: Germania
Garantía: 12 Meses
Inscriptio electronica: [email protected]
whatsapp: +86-18150117685
- Conspectus
- Product Overview
- Key Functions
- Official Specifications
- Quaestiones Frequenter Rogatae
- Compatibility & Ordering Notes
- Hot Selling Models
- Producta commendata
Conspectus
Siemens · SIMATIC TeleService
6ES7972-0CB35-0XA0 TS Adapter II Analog Modem
Siemens 6ES7972-0CB35-0XA0 is the SIMATIC TS Adapter II with an integrated analog modem, RS-485 connection to MPI/DP, USB parameterization and optional external 24 V DC supply.
Ad Primum Aspectum
| Nota | Siemens |
|---|---|
| Modellum | 6ES7972-0CB35-0XA0 |
| Typus Producti | Remote-service adapter with integrated analog modem |
| Functio principalis | Providet accessum remotum ad stationes automationis MPI/PROFIBUS per rete telephonicum analogicum |
| Applicatio vel series compatibiles | Systemata SIMATIC S7 et C7 utentia software TeleService |
Approbatio civitatis
Confirmet ut operatio modemi integrati permittatur in patria installationis.
Coniunctio Bus
Servet adressem MPI vel PROFIBUS, velocitatem baud, caleum et dispositionem terminationis externae.
Aditum Remotum
Transferet parametres initialisationis modemi, parametres compositionis, controllem accessus et parametres conexionis TeleService.
Product Overview
Siemens 6ES7972-0CB35-0XA0 is the SIMATIC TS Adapter II with an integrated analog modem, RS-485 connection to MPI/DP, USB parameterization and optional external 24 V DC supply.
Modem integratus suadet manutenzionem per compositionem telephonici in rete telephonicum analogicum approbatum. Portus RS-485 connectit adaptatorem ad systemata automationis SIMATIC S7 vel C7. USB 1.1 suadet parameterisationem localem et programmationem dispositivorum connexorum.
Key Functions
Servitium Remotum Analogicum
Modem integratus suadet manutenzionem per compositionem telephonici in rete telephonicum analogicum approbatum.
Interfacies MPI/DP
Portus RS-485 connectit adaptatorem ad systemata automationis SIMATIC S7 aut C7.
Parameterizatio per USB
USB 1.1 permittit parameterizationem localem et programmationem dispositivorum connexorum.
Official Specifications
| Designatio producti | Modem TS Adapter II |
|---|---|
| Interfacs Automationis | RS-485 pro MPI/PROFIBUS DP |
| Maxima velocitas bus automationis | 12 Mbit/s |
| PC Interface | USB 1.1 |
| Velocitas USB | 12 Mbit/s |
| Interfacies modem externi | RS-232 |
| Maxima velocitas RS-232 | 115 kbit/s |
| Analog Network Connector | RJ12 |
| Alimentātiō externa | 24 V DC SELV |
| Permissum Supplicationis Intervallum | 20,4 ad 28,8 V DC |
| Power from MPI Interface | Supportata |
| Consumptio Electrica Typica | 44 mA |
| Maxima Consumptio Electrica | 120 mA |
| Maxima Currus Inrumpens | 700 mA for 8 µs |
| Dimensiones | Approximately 125 x 110 x 40 mm |
| Pondus | Circa 250 g |
| Dial Procedures | DTMF and pulse dialing |
| Modem Command Set | Hayes AT |
| Correctio Errorum et Compressio | Supportata |
| Ciclus vitae | Partes de reposito / cancellatio producti |
Quaestiones Frequenter Rogatae
Quae rete SIMATIC per 6ES7972-0CB35-0XA0 adire possum?
Interfacies RS-485 connectitur ad stationes automationis MPI et PROFIBUS DP supportatas.
Quomodo 6ES7972-0CB35-0XA0 parametratur localiter?
Utere coniunctione USB 1.1 cum ambiente configurationis TeleService idoneo.
Num 6ES7972-0CB35-0XA0 potest vim accipere ab adiuncto bus?
Ita, per interfaciem MPI aut ex fonte externa 24-volt SELV suppleri potest.
Quae coniunctio telefonica ab 6ES7972-0CB35-0XA0 utitur?
Modemus analogus integratus connectitur ad rete telephonicum per interfaciem RJ12.
Cur patria installationis inspicienda est pro 6ES7972-0CB35-0XA0?
Approbatio telecommunicationum et parametri modemus permisi variant secundum patriam.
Quid servare debes antequam 6ES7972-0CB35-0XA0 substituis?
Serva parametres bus, initialisationem modemus, informationem de numerando, controllem accessus et constitutionem connexionis TeleService.
Quid experiri debes post installationem 6ES7972-0CB35-0XA0?
Experire accessum localem per USB, communicationem bus, voces emissas et receptas, authenticationem et sessionem remotam regulatam.
Compatibility & Ordering Notes
Index Compatibilitatis
- Usus variantis modemus solum ubi eius approbatio analogica telecommunicationum et connexio rete valida sunt.
- Adaequa MPI aut PROFIBUS adressem, velocitatem, calebum, terminationem et constitutionem stationis.
- Restaurare parametri modem: initializatio, numeratio, securitas, et parameters TeleService ante usum remotum.