- Conspectus
- Hot Selling Models
- Producta commendata
Conspectus
- Use un cable de instalación PROFIBUS FastConnect de dos conductores compatible y la disposición especificada para la preparación del cable.
- Inserte ambos conductores por completo, cierre por completo la cubierta de contacto de desplazamiento de aislamiento y asegure el alojamiento.
- Assure that the bare cable shield touches the designated shield element.
- Set the integrated resistor switch to the segment position, considering disconnection of the outgoing PROFIBUS path when ON.
- For reconnection, cut back the previously terminated cable end and stay within the ten-cycle contact limit.
6ES7972-0BB52-0XA0 SIMATIC PROFIBUS FastConnect 90° Connector with PG Socket
A 90° PROFIBUS FastConnect connector with two cable entries, a 9-pin D-sub device interface and a separate PG socket.
Ad Primum Aspectum
| Nota | Siemens |
|---|---|
| Modellum | 6ES7972-0BB52-0XA0 |
| Typus Producti | RS485 bus connector |
| Functio principalis | Joining a station to the PROFIBUS bus |
| Applicatio | Electrical PROFIBUS networks |
FastConnect assembly
Insulation displacement contacts terminate the two-core PROFIBUS FC cable.
Segment termination
A slide switch connects the integrated resistor combination.
Service Access
The PG socket provides a programming-device connection at the bus plug.
Product Overview
6ES7972-0BB52-0XA0 Connects a PROFIBUS station to the electrical bus using FastConnect insulation-displacement contacts and a 90° cable outlet.
The connector provides two bus-cable connections, an integrated switchable terminating resistor and a PG socket, with the termination-switch position also affecting continuity to downstream stations.
Key Functions
Terminate the cable without separate wire stripping.
Insert the green and red conductors fully into the open contact cover and close the cover completely to make the FastConnect connection.
Switch the segment-end resistor network.
The integrated resistor combination is selected by a slide switch, and setting the switch to ON disconnects the PROFIBUS path to the other stations at that point.
Maintain the shield and service connection.
The exposed cable shield rests on the connector’s contact element, while the PG socket provides the additional programming interface.
Official Specifications
| Velocitat de dades PROFIBUS | 9.6 kbit/s–12 Mbit/s |
|---|---|
| Bus-Cable Connections | 2 |
| Device Interface | 1 × 9-pin D-sub connector |
| Terminatio Cables | Integrated insulation-displacement contacts for two-core PROFIBUS FC installation cable |
| Cable outlet angle | 90° |
| Terminatio Bus | Combinatio resistorum integrata selecta per interruptorem glissans |
| PG Connection | Additional PG socket |
| Enclosure and Locking | Plastic enclosure; screw locking |
| Abmessungen (Breite × Höhe × Tiefe) | 15,8 × 59 × 35,6 mm |
| Ponderis netum | 45 g |
| Operans ambientium temperatus | −25 usque ad +60 °C |
| Temperatura servandi et transportandi | −40 usque ad +70 °C |
| Gradus praesidium | IP20 |
| Remissio tensionis cavi | Integrated |
| Silicone Content | Sine silicio |
| Insulation-Displacement Contact Endurance | 10 cycli terminales |
Quaestiones Frequenter Rogatae
Cur interrumpit commutatio 6ES7972-0BB52-0XA0 ad positionem ON communicationem ad stationes subsequentes?
Positio ON connectit resistentiam terminalem et disconectit continuationem PROFIBUS ad alias stationes in illo puncto.
Num possum eundem extremum fili secti rursus connecere in 6ES792-0BB52-0XA0 postquam contactus aperuerint?
Linea quae iam est connecta debet esse recisa antequam rursus connectatur ad contactus displacementis isolationis.
Quot cycli reconnectionis contactus in 6ES7972-0BB52-0XA0 sunt designati?
Terminales displacementis isolationis sunt designati pro decem cyclis terminalibus.
Ubi scutum cavi debet tangere 6ES7972-0BB52-0XA0?
Scutum expositum debet esse nudum ubi super elementum contactus scuti connectoris requiescit.
Quousque conductores in tegumentum contactus 6ES7972-0BB52-0XA0 impellendi sunt?
Inserte los cables verde y rojo tan lejos como sea posible y cierre completamente la cubierta de contacto.
¿Puedo usar una conexión PG directamente en 6ES7972-0BB52-0XA0?
El conector incluye un zócalo PG separado para la conexión del dispositivo de programación.
¿Qué ángulo de recorrido de cable debo dejar detrás de la estación al instalar 6ES7972-0BB52-0XA0?
El conector tiene una salida de cable a 90° y una profundidad del cuerpo de 35,6 mm.