Siemens 6ES7222-1HF22-0XA8 SIMATIC S7-200 CN EM 222 Octo-Relais-Ausgangsmodul
Fabricator: Siemens
Condición: Nuevo
Plazo de Entrega: En Stock
Origo: Germania
Garantía: 12 Meses
Inscriptio electronica: [email protected]
whatsapp: +86-18150117685
- Conspectus
- Hot Selling Models
- Producta commendata
Conspectus
- Conformare totum numerum articuli CN et dispositionem octo releorum.
- Praebere alimentationem bobinae relei 20,4–28,8 V DC.
- Tenere singulum output intra 2 A et singulam communitatem intra 10 A.
- Praebere externam protectionem contra curtum circuitum et non iungere outputs releorum in parallello.
- Cavere vitam commutationis releorum et minuere impetum accensionis lampadum infra rating impetus output.
6ES7222-1HF22-0XA8 SIMATIC S7-200 CN EM 222 Octo-Relay Output Module
An EM 222 expansion module featuring eight dry-contact relay outputs, a 2 A per-point rating, and a dedicated 24 V DC supply for relay coils.
Ad Primum Aspectum
| Nota | Siemens |
|---|---|
| Modellum | 6ES7222-1HF22-0XA8 |
| Typus Producti | Digital expansion module |
| Functio principalis | Extending PLC-controlled load circuits |
| Applicatio | Compatible S7-22X CPU assemblies |
Octo canales relectorum
Dry contacts switch AC or DC load circuits within the specified voltage limits.
Separate coil power
The relay coils operate on a 20.4–28.8 V DC supply.
Circuits de onus aggregati
Both the 2 A per-point limit and the 10 A common limit apply.
Product Overview
6ES7222-1HF22-0XA8 adds eight relay-switched output channels to a compatible S7-200 CN controller. Each dry contact has a 2 A rated output current, with the relay coil circuit powered separately at 24 V DC.
The contacts can switch DC and AC loads within their respective voltage ranges. Relay switching speed, contact life, lamp inrush and external short-circuit protection are important when selecting the field circuits.
Key Functions
Switch AC or DC loads
The dry contacts operate over 5–30 V DC or 5–250 V AC.
Expand the output bank
Eight relay channels add discrete load-control points to the CPU expansion assembly.
Separate coil and contact circuits
The relay coil-to-contact isolation is tested at 1500 V AC for one minute.
Official Specifications
| Emissiones Relais | 8 |
|---|---|
| Rated current per output | 2 A |
| Maxima Currus per Commune | 10 A |
| Contact working-voltage range | 5–30 V DC aut 5–250 V AC |
| Relay-coil supply range | 20,4–28,8 V CC |
| 5 V DC bus current | 40 mA |
| 24 V DC coil current | 9 mA per energized output |
| Perdita de Potentia Typical del Modulo | 2 W |
| Maximum output surge | 5 A for 4 s at 10% duty cycle |
| Maximum new-contact resistance | 0.2 Ω |
| Maximum relay switching time | 10 ms |
| Frequentia Maxima Commutandi | 1 Hz |
| Mechanical life at no load | 10000000 cycles |
| Durata contactuum ad onus nominale | 100000 cycli |
| Coil-to-contact isolation test | 1500 V AC per 1 mīnutam |
| Longitudo Maxima Cavi Exientis | 500 m scutum; 150 m non scutum |
| Simultaneous output operation | Omnia output ad 55 °C horizontaliter vel 45 °C verticaliter |
| Protectionem contra curtum circuitum effluxus integratam habet | Nullus |
| Dimensiones custodis | 45 × 80 × 62 mm (latus × altitudo × profunditas) |
Quaestiones Frequenter Rogatae
Num utriusque circuitus oneris AC et DC commutare possum cum 6ES7222-1HF22-0XA8?
Output dry-contact operant intra 5–30 V DC aut 5–250 V AC.
Quae limitatio currentis ad communem partitam in 6ES7222-1HF22-0XA8 applicatur?
Unusquisque communis ad 10 A limitatur, et unumquodque output singulare intra suum rating 2 A manere debet.
May I connect relay outputs of 6ES7222-1HF22-0XA8 in parallel to increase the load current?
Parallel connection of two relay outputs is not permitted.
Is 6ES7222-1HF22-0XA8 suitable for a fast pulse-output application?
The relay output has a maximum switching frequency of 1 Hz and a maximum switching time of 10 ms.
Which supply must I provide for the relay coils of 6ES7222-1HF22-0XA8?
Supply the coil circuit with 20.4–28.8 V DC and allow 9 mA for each energized output.
How far may I run the output cables from 6ES7222-1HF22-0XA8?
The maximum output cable length is 500 m when shielded or 150 m when unshielded.
What lamp-load inrush should I consider when using 6ES7222-1HF22-0XA8?
Keep lamp turn-on surge below the 5 A output surge rating because excessive inrush can reduce relay life by 75%.