SIEMENS SIMATIC ET 200SP

6ES7193-6PA00-0AA0 ET 200SP Server Module

A 7 mm wide ET 200SP bus-end module with slot-voltage status functions and a holder for three spare 5 × 20 mm fuses.

Ad Primum Aspectum

Nota Siemens
Modellum 6ES7193-6PA00-0AA0
Typus Producti ET 200SP server module
Functio principalis Closes the station backplane bus and provides configured slot-voltage status data
Applicatio Termination and status supervision of ET 200SP stations

Backplane bus completion

The server module closes the ET 200SP backplane bus.

Slot status information

Configured input data represents supply and supported feedback-voltage status.

Spare fuse holder

Un support incorporatus conservat tres fusibiles de recambium 5 × 20 mm.

Product Overview

6ES7193-6PA00-0AA0 completat bus dorsalem ET 200SP et sustinet monitorationem configuratam status tensionis alimentationis et status tensionis retroactionis modulorum I/O.

Modulus compactus sustinet actualisationes firmware, datos identificationis I&M et reconfigurationem in statu RUN, cum tenaculo pro tribus fusibilibus de recambium et memoria retentiva pro nomine dispositivi pro ordinibus substitutionis IM 155-6 PN BA supportatis.

Focus ordinandi: Adaptate statum configurationis dati ET 200SP CPU aut moduli interfacialis, statum configurationis dati status et gradum firmware requisitum pro retentione nominis dispositivi IM 155-6 PN BA.
Key Functions

Backplane bus completion

Modulus servitor claudit bus dorsalem ET 200SP ad extremum stationis.

Status tensionis alimentationis et retroactionis

Data input configurata indicant absentiam tensionis alimentationis vel absentiam modulorum I/O et, ubi a modulo I/O supportatur, tensionem retroactionis.

Supportus pro servitio et substitutione

Modulus praebet data I&M et actualizationem firmware; tamen productum versionis 1 cum firmware V1.1.1 aut posterioribus suadet retentivam conservationem nominis dispositivi pro substitutione IM 155-6 PN BA absque configuratione topologica.

Official Specifications
Maxima Consumptio Electrica 30 mA
Altitudo rae montationis 7.5 mm aut 15 mm
Temperatura operationis pro installatione horizontali −30 to +60 °C
Temperatura operationis pro installatione verticali −30 to +50 °C
Altitudo Installationis Maxima 5 000 m; restrictiones installationis valent supra 2 000 m
Minimum Dew Point −60 °C; suitable for dry-room applications
Dimensiones (L × H × D) 7 × 117 × 36 mm
Pondus Approximatum 19 g
Spare fuse holder Tres fusibiles, 5 × 20 mm
Data input pro statu tensionis alimentationis tantum 2, 4 aut 8 octeta pro configurationibus maximis CPU/interface de 12, 32 aut 64 locis I/O respective
Data input pro statu tensionis alimentationis et tensionis retroactionis 4, 8 aut 16 octetis pro configurationibus maximis CPU/interfacii: 12, 32 aut 64 fendas I/O respective
Limen detectionis tensionis retroactionis Modulus I/O L+ maior quam 6 V, cum monitoratione retroactionis supportata
Requisitum retentionis nominis dispositivi IM 155-6 PN BA Versio producti moduli serveris ≥1 et firmware ≥V1.1.1
Quaestiones Frequenter Rogatae

Ubi 6ES7193-6PA00-0AA0 in statione ET 200SP locatur?

Modulus serveris claudit bus plani dorsalis ad extremum stationis ET 200SP.

Quae magnitudo fusibilis in 6ES7193-6PA00-0AA0 reponi potest?

The integrated holder accommodates three spare fuses measuring 5 × 20 mm.

Which version of 6ES7193-6PA00-0AA0 supports device-name retention for IM 155-6 PN BA replacement?

This function requires product version 1 or later with firmware V1.1.1 or later.

How many input bytes does 6ES7193-6PA00-0AA0 need for both voltage-status functions in a 32-slot configuration?

A CPU or interface module with a maximum configuration of 32 I/O modules uses eight input bytes when both supply-voltage and feedback-voltage status are enabled.

Can 6ES7193-6PA00-0AA0 evaluate feedback voltage from every ET 200SP I/O module?

The I/O module must support feedback-voltage monitoring for that status to be evaluated.

Which engineering methods can configure 6ES7193-6PA00-0AA0?

The module can be configured with STEP 7 in TIA Portal or with a GSD file.

Is the full 60 °C upper ambient limit valid for a vertical installation of 6ES7193-6PA00-0AA0?

The upper limit is 60 °C for horizontal installation and 50 °C for vertical installation, with a lower limit of −30 °C in both orientations.

Compatibility & Ordering Notes
Before ordering 6ES7193-6PA00-0AA0: Select the server module for the ET 200SP station end and match the CPU or interface-module configuration, enabled status functions and firmware-dependent replacement features.

Compatibility Checklist for 6ES7193-6PA00-0AA0

  • Install at the ET 200SP backplane-bus end.
  • Use a mounting rail with a supported 7.5 mm or 15 mm height.
  • Choose the supply and feedback-voltage status configuration and allocate its input bytes.
  • Use I/O modules with the required monitoring capability.
  • Use product version ≥1 and firmware ≥V1.1.1 for the IM 155-6 PN BA device-name retention function.
  • Observe orientation-specific temperatures and altitude restrictions.
Hot Selling Models
H07V-K
6ES5497-4UB42
CBX100 93A301067
WTE11-2P2432 1041381 1748
22-S-M8-PNP
EL2622
A-5003-7306
NBB8-F33-E2
1-KAB 176-2 1-CON-P3001
BR-090.03,540,UR
1784180000
6ES7134-0HF01-0XB0
SPAB-B2R-G18-PB-M8
Helukabel 26497
FES-M-11

Accipe Aestimationem Gratuitam

Legatus noster te mox contactabit.
Epistula electronica
Nomen
Nomen societatis
Nuntius
0/1000
epistula electronica ad Summum ire

Evolo Automation non est distributor autorizatus nisi aliter specificatum, nec representans, nec affinis fabricantis huius producti. Omnia signa propria et documenta sunt proprietatis suorum dominorum respective et data sunt ad identificationem et informationem.