Siemens SIMATIC ET 200X EM 144 Analog Input Module 6ES7144-1FB31-0XB0
Fabricator: Siemens
Condición: Nuevo
Plazo de Entrega: En Stock
Origo: Germania
Garantía: 12 Meses
Inscriptio electronica: [email protected]
whatsapp: +86-18150117685
- Conspectus
- Product Overview
- Key Functions
- Official Specifications
- Quaestiones Frequenter Rogatae
- Compatibility & Ordering Notes
- Hot Selling Models
- Producta commendata
Conspectus
SIEMENS · SIMATIC ET 200X
6ES7144-1FB31-0XB0 SIMATIC ET 200X EM 144 Analog Input Module
The ET 200X EM 144 analog input expansion module acquires two ±10 V signals with 12-bit-plus-sign resolution and provides channel diagnostics in an IP66/IP67 field installation.
Ad Primum Aspectum
| Nota | Siemens |
|---|---|
| Modellum | 6ES7144-1FB31-0XB0 |
| Typus Producti | Two-channel analog input expansion module |
| Functio principalis | Acquires two bipolar voltage signals in a distributed ET 200X station |
| Applicatio vel series compatibiles | ET 200X distributed I/O installations requiring two ±10 V analog inputs with channel diagnostics |
Identificatio exacta.
Conformare character per character il codice 6ES7144-1FB31-0XB0 e confermare la completa denominazione del modulo di ingresso analogico SIMATIC ET 200X EM 144.
Arrangementum Interfacis
Confirmare ante connexionem substitutionis supplitum installatum, portus, connexiones campestres et accessoria requisa.
Configuration Check
Servare projectum ingenieriae approbatum, parametres rete et data applicationis quae systema installatum utitur.
Product Overview
The ET 200X EM 144 analog input expansion module acquires two ±10 V signals with 12-bit-plus-sign resolution and provides channel diagnostics in an IP66/IP67 field installation.
Due canali acquisiscono segnali di processo bipolari nella gamma ±10 V. I guasti sui canali possono generare diagnosi e allarmi di processo configurati. I connettori M12 e la protezione IP66/IP67 supportano l’installazione decentrata sulla macchina.
Key Functions
Due ingressi di tensione
Due canali acquisiscono segnali di processo bipolari nella gamma ±10 V.
Diagnostica integrata
I guasti sui canali possono generare diagnosi e allarmi di processo configurati.
Design per montaggio in campo
I connettori M12 e la protezione IP66/IP67 supportano l’installazione decentrata sulla macchina.
Official Specifications
| INPUTUS ANALOGI | 2 canali di ingresso tensione |
| Ambitus Input | ±10 V |
| Resolutio | 12 bitoj plus signo |
| Isolatio Canalium | Nessuna isolazione galvanica |
| Connection initus | Duo foraminula M12 quattuor-pin, X1 et X2 |
| Indicatio Erroris Gruppi | LED Ruber SF |
| Alarma Diagnostica et Processualia | Parametrizabilis |
| Reiectiō Modī Communis | > 60 dB |
| Reiectiō Modī Normalis | > 40 dB |
| Limitis Erroris Operativi | ±1.2% per ambitum temperaturarum specificatum |
| Basic Error Limit | ±1.0% ad 25 °C |
| Error Temperaturae | ±0.01%/K |
| Crosstalk entre entradas | > 45 dB |
| Longitudo Cavi Scutati | Maxime 30 m |
| Gradus praesidium | IP65, IP66 aut IP67 cum foraminulis non usitatis obstruis |
| Dimensiones et Pondera | 87 × 110 × 55 mm (L × A × P); circiter 250 g |
| Maxima Consumptio Electrica | 40 mA |
| Ammissio Potentiae | Typice 0.9 W |
Quaestiones Frequenter Rogatae
Quot canales analogici sunt in 6ES7144-1FB31-0XB0?
Duo canales intrantes praebentur.
Quae latitudo signali ad 6ES7144-1FB31-0XB0 coniungenda est?
Signa tensionis bipolaria intra specificatam latitudinem mensurandi ±10 V utere.
Num canales 6ES7144-1FB31-0XB0 ab invicem isolati sunt electrico modo?
Non; terram sensorum et relationes potentialium commode disponere oportet.
Num 6ES7144-1FB31-0XB0 defectus canalium nuntiare potest?
Ita; diagnostics et alarmas necessarias in configuratione stationis activare oportet.
Quales connexiones utuntur 6ES7144-1FB31-0XB0?
Utere approbatis connexiones campi M12 et observa attributum pinarum documentatum.
Quae protectio environmentalis ad 6ES7144-1FB31-0XB0 pertinet?
Connexiones et signa recte compositae favent protectionem campi IP66 et IP67.
Quid inspiciendum est post substitutionem 6ES7144-1FB31-0XB0?
Verifica connexionem canalium, scalationem, terram, diagnosticam, alarmes limitum et valores mensos.
Compatibility & Ordering Notes
Index Compatibilitatis
- Utere approbata statione basi ET 200X et dispositione extensionis.
- Adaptare connexionem M12, intervalla ±10 V et potentiale referentiae commune.
- Restitue diagnosticam canalium et parametra limitum antequam validatio fiat.