Conspectus
- Order the CM IO connection face separately and use the pin assignment for this mixed module.
- Keep output loads within 0.5 A per channel and 2 A per group.
- Limit unshielded input and output cables to 30 m.
- Utere pino 1 pro suppetitione encoderis ab 2L+, pino 3 pro 2M, et pino 5 pro terra functionali in modulis connexionis M12 enumeratis.
6ES7143-4BF50-0AA0 SIMATIC ET 200pro 4DI/4DO Digital I/O Module
Four digital inputs and four 0.5 A outputs share a 24 V DC electronic module with short-circuit diagnostics.
Ad Primum Aspectum
| Nota | Siemens |
|---|---|
| Modellum | 6ES7143-4BF50-0AA0 |
| Typus Producti | Mixed digital electronic module |
| Functio principalis | Acquire sensors and switch field actuators |
| Applicatio | ET 200pro distributed I/O stations |
Mixed field signals
Four inputs and four outputs combine sensing and actuation.
Protected outputs
Electronic short-circuit protection is provided per output channel.
Separate connection face
Select the matching M12 connection module for the field cables.
Product Overview
6ES7143-4BF50-0AA0 combines four P-reading digital inputs with four current-sourcing 24 V DC outputs in the ET 200pro system.
The inputs and output loads are supplied from 2L+, and the output channels are rated at 0.5 A each. Short-circuit diagnostics and green channel status indicators support local fault checks.
Key Functions
Read sensors at the machine
The four inputs use IEC 61131 Type 3 characteristics and accept two-wire sensors with a maximum 1.5 mA quiescent current.
Control DC actuators
The four outputs can operate solenoid valves, DC contactors and indicator lamps within the 0.5 A per-channel limit.
Locate output and supply faults
Informatio diagnosticas disponibilis est pro circuitus breves output et circuitus breves suppletionis encoder, simul cum indicatione status input et output viridis.
Official Specifications
| Canalis Input Digitalis et Output | 4 input et 4 output current-sourcing |
|---|---|
| Tensio Nominalis et Tensio Input | 24 V DC |
| Limina Signali Inputii | Signum 0: −3 ad +5 V; signum 1: +11 ad +30 V |
| Caracteristica input | Lectura P; Typus IEC 61131-3 |
| Typica introitus currentis signi-1 | 7 mA |
| Délai d’entrée maximal | 3 ms pro utroque transitione |
| Maxima Cabello Campo Non Scutata | 30 m pro input et output |
| Currentis Output Aestimatus | 0,5 A per canalēm |
| Totus Currus Exitus | 2 A per gruppus usque ad 55°C, omnes positiones montandi |
| Minimum voltatio output signi-1 | 2L+ − 0.8 V |
| Maximum OFF-State Residual Current | 0,5 mA |
| Protectio contra curtum circuitum in effluenti | Electronic per channel; typical threshold 0.7 A |
| Limitis Tensionis Inductivae ad Desactivationem | Typically 2L+ − 47 V |
| Frequentia Maxima Commutandi | Resistive: 100 Hz; inductive: 0.5 Hz; lamp: 1 Hz |
| Maxima onus lampadis | 5 w |
| Currentis Alimentatio Encoderis | 1 A maximum up to 55°C |
| Perditio potentiæ typica | 2 W |
| Backplane Isolation | Isolated from all other circuit components; 707 V DC type test |
| Indicatio status canalium | Green LEDs for digital inputs and outputs |
| Dimensiones et Pondera | 45 × 130 × 35 mm (W × H × D); approximately 140 g |
Quaestiones Frequenter Rogatae
Does 6ES7143-4BF50-0AA0 come with the field connection module?
No, the bus module is included but the I/O connection module must be ordered separately.
Can I use 6ES7143-4BF50-0AA0 with the CM IO 4xM12 connection face?
Yes, CM IO 4xM12 and CM IO 4xM12P connection modules provide the listed four-socket field connection.
Which pins carry the input and output signals for 6ES7143-4BF50-0AA0?
On each of the four M12 sockets, pin 4 carries the digital input and pin 2 carries the corresponding digital output.
Can I parallel outputs on 6ES7143-4BF50-0AA0 to obtain more than 0.5 A?
No, parallel operation is allowed for redundant load control but not to increase output current.
Will 6ES7143-4BF50-0AA0 accept a two-wire sensor?
Yes, a two-wire sensor can be connected when its quiescent current does not exceed 1.5 mA.
What lamp load can one output of 6ES7143-4BF50-0AA0 switch?
The maximum lamp load is 5 W.
How quickly can 6ES7143-4BF50-0AA0 switch an inductive actuator?
Frequentia maxima commutandi pro onere inductivo est 0.5 Hz.