Siemens 6ES7138-4FB03-0AB0 ET 200S 4 F-DO 24 V DC 2 A Module
Fabricator: Siemens
Condición: Nuevo
Plazo de Entrega: En Stock
Origo: Germania
Garantía: 12 Meses
Inscriptio electronica: [email protected]
whatsapp: +86-18150117685
- Conspectus
- Hot Selling Models
- Producta commendata
Conspectus
- Dimensio singulae actuatoris pro minimo onere 20 mA et pro corrente canalium nominata 2 A.
- Applica limites currentis totalis pro directione installationis reali et pro temperatura ambienti.
- Non conecte outputs in parallelum nec utere eos ad regendos intrusus digitales.
- Utere idoneo interfacie stationis PROFIsafe et serva rectam polaritatem subministrationis 24 V DC.
6ES7138-4FB03-0AB0 ET 200S 4 F-DO 24 V DC 2 A Module
Quattuor outputus transistoris tuti cum valore canalium 2 A, facultas tutelae usque ad SIL 3 et latitudo moduli 30 mm.
Ad Primum Aspectum
| Nota | Siemens |
|---|---|
| Modellum | 6ES7138-4FB03-0AB0 |
| Typus Producti | Electronica tutela outputorum |
| Functio principalis | Commutare onera DC fallaciter tutata |
| Applicatio | Circuitus actuatoris ET 200S PROFIsafe |
Outputus actuatoris tuti
Quattuor outputus transistoris contra curtum circuitum tuti praebent currentem nominalem 2 A per canalem.
Temperature-dependent load capacity
Maxima summa currentium outputorum est 6 A ad temperaturam ambientem usque ad 40 °C in positione horizontali, minuens ad temperaturas ambientes altiores.
Visibilitas defectus
Diagnostics pro defectu corto-circuitu et pro interruptura fili sunt accompaniati ab LED rubro pro defectu gruppalis et ab LED viridibus pro statu output.
Product Overview
6ES7138-4FB03-0AB0 interruptores faciunt onera 24 V DC fail-safe per quattuor canales output transistorum in statione ET 200S.
Selectio oneris debet rationem habere de minimo currente commutato, de limite totali currentis et de reductione pro temperatura ambienti, non solum de valore canalis.
Key Functions
Outputus actuatoris tuti
Quattuor outputus transistoris contra curtum circuitum tuti praebent currentem nominalem 2 A per canalem.
Temperature-dependent load capacity
Maxima summa currentium outputorum est 6 A ad temperaturam ambientem usque ad 40 °C in positione horizontali, minuens ad temperaturas ambientes altiores.
Visibilitas defectus
Diagnostics pro defectu corto-circuitu et pro interruptura fili sunt accompaniati ab LED rubro pro defectu gruppalis et ab LED viridibus pro statu output.
Official Specifications
| Alimentatio oneris nominalis | 24 V DC |
|---|---|
| Currentis typicus supplicationis | 100 mA ab L+ sine onere |
| Currentis Maxima Planae Posterioris | 28 mA ad 3.3 V |
| Perditio potentiæ typica | 3.5 W |
| Output construction | 4 output transistorum protegiti contra corto-circuitum |
| Currentis Output Aestimatus | 2 A per canalium |
| Currente signi 1 permittenda | 20 mA–2.4 A |
| Tensio signi 1 in effusione | Saltem L+ minus 2 V |
| Maximum Off-State Leakage | Interruptor P: 0,5 mA; interruptor M: 4 mA |
| Maxima onus lampadis | 10 W |
| Permitted Load Resistance | 12 Ω–1 kΩ |
| Commutatione Frequency | Resistivus: 30 Hz; inductivus: 0,1 Hz; lampis: 10 Hz |
| Currentis outputus combinatus, horizontalis | 6 A usque ad 40 °C; 5 A usque ad 55 °C; 4 A usque ad 60 °C |
| Currentis outputus combinatus, verticalis | 4 A usque ad 40 °C |
| Maxima longitudo cavi actuatoris | 200 m, cum scuto aut sine scuto |
| Operatio Exitus Parallelis | Non permittitur pro incremento currentis aut pro controllo oneris redundantis |
| Capacitas Securitatis | Usque ad SIL 3, Categoria 4 et PL e |
| Tensio Probae Isolationis | 500 V DC |
| Protectio ab polaritate inversa | Non praebita |
| Dīmēnsiōnēs et massa apprōximāta | 30 × 81 × 52 mm; 85 g |
Quaestiones Frequenter Rogatae
Can I use 6ES7138-4FB03-0AB0 to drive a PLC digital input?
Controlling a digital input is not supported by this output module.
Can I parallel two channels of 6ES7138-4FB03-0AB0 to increase current?
Parallel operation is not permitted for either higher current or redundant load control.
Will 6ES7138-4FB03-0AB0 work with an actuator drawing less than 20 mA?
The permitted signal 1 load current starts at 20 mA.
How much current can 6ES7138-4FB03-0AB0 switch at 60 °C in a horizontal station?
The combined output current is limited to 4 A at an ambient temperature of 60 °C.
Can I connect a 15 W lamp directly to 6ES7138-4FB03-0AB0?
Maxima permitita lampae onus est 10 W.
Habetne off output 6ES7138-4FB03-0AB0 nullam fugam currentis?
Maxima fuga in statu off est 0.5 mA pro commutatore P et 4 mA pro commutatore M.
Quod interfaciem ET 200S permittit 6ES7138-4FB03-0AB0 uti PROFINET?
Modulus interfaciei IM151-3 HF permittit coniunctionem stationis PROFINET.