- Conspectus
- Hot Selling Models
- Producta commendata
Conspectus
- Utere BaseUnit A0 et serva dispositionem electronicam codificationis typi F.
- Cura ut totale modulus 6 A et limites canalis singuli 2 A includantur.
- Applica limitem temperaturae horizontalis aut verticalis et deductionem applicabilem.
- Verifica applicationem integram fail-safe antequam circuitus actuatoris in operationem mittantur.
6ES7136-6DB00-0CA0 SIMATIC ET 200SP F-DQ 4x24VDC/2A PM HF Safety Output Module
A four-channel 24 V DC safety output module rated at 2 A per channel, with automatic F coding and capability up to PL e / SIL 3.
Ad Primum Aspectum
| Nota | Siemens |
|---|---|
| Modellum | 6ES7136-6DB00-0CA0 |
| Typus Producti | Fail-safe digital output electronics module |
| Functio principalis | Switching safety-related DC actuators |
| Applicatio | ET 200SP fail-safe I/O stations |
Switch fail-safe actuator circuits
Four parameterizable transistor outputs each carry up to 2 A, subject to the module total and thermal derating.
Detect output-circuit faults
Open-circuit, overload and short-circuit detection support channel fault handling.
Integrate into a safety station
The module supports engineering from TIA Portal V12 or STEP 7 V5.5 SP3 and uses automatic F-type electronic coding.
Product Overview
6ES7136-6DB00-0CA0 provides four transistor outputs for fail-safe ET 200SP applications. The F-DQ PM HF module uses an A0 BaseUnit and an F-type electronic coding element.
Diagnostics include open-circuit, overload and short-circuit detection, complemented by channel and module indicators. The achievable safety capability extends to PL e and SIL 3 within the applicable safety configuration.
Key Functions
Switch fail-safe actuator circuits
Four parameterizable transistor outputs each carry up to 2 A, subject to the module total and thermal derating.
Detect output-circuit faults
Open-circuit, overload and short-circuit detection support channel fault handling.
Integrate into a safety station
The module supports engineering from TIA Portal V12 or STEP 7 V5.5 SP3 and uses automatic F-type electronic coding.
Official Specifications
| Output channels and switching technology | 4 transistor outputs |
|---|---|
| Praebere notam et ambitum operativum | 24 V DC; 19,2–28,8 V DC |
| Consumptione de Currente sine Onere | 75 mA notatum |
| Consumption of backplane | Maximum 21 mA; 70 mW |
| Typica damnum moduli | 4 W |
| Processus allocationis adressionum | 5 octeta input et 5 octeta output |
| Rated current per output | 2 A |
| Maximum current totius moduli | 6 A, subiectum deductioni |
| Maximum OFF-State Residual Current | 0,5 mA |
| Intervalum Resistentiae Onus | 12–2 000 Ω |
| Maxima onus lampadis | 10 W |
| Typicum limen circuitus aperti | 8 mA |
| Typicum limen supercarricaturae | 2,9 A |
| Typical Short-Circuit Response Threshold | Maior quam 3,3 A |
| Maximae rates commutationis symmetricae | 30 Hz resistivus; 0,1 Hz inductivus DC-13; 10 Hz oneris lampae |
| Longitudines maximae cableorum output | 1 000 m scutatus; 500 m non scutatus |
| Examen Isolationis | examen typicum 707 V CC |
| Maximae classes securitatis consequibiles | PL e ad ISO 13849-1; SIL 3 ad IEC 61508 |
| Temperatura Operativa secundum Positionem | 0–60 °C horizontaliter; 0–50 °C verticaliter |
| Dimensiōnēs Moduli et Pōns Apprōximātus | 15 × 73 × 58 mm; 57 g |
Quaestiones Frequenter Rogatae
Quod genus BaseUnit requiritur pro 6ES7136-6DB00-0CA0?
Hoc modulum requirit BaseUnit generis A0.
Num omnes quattuor canales 6ES7136-6DB00-0CA0 simul continuo 2 A praebere possunt?
The module total is limited to 6 A and remains subject to thermal derating.
What project address space should I allow for 6ES7136-6DB00-0CA0?
Reserve five input bytes and five output bytes.
Which engineering versions can configure 6ES7136-6DB00-0CA0?
Configuration is available from TIA Portal V12 or STEP 7 V5.5 SP3.
Will 6ES7136-6DB00-0CA0 detect a disconnected actuator circuit?
The module provides open-circuit detection with a typical 8 mA threshold.
Can I use 6ES7136-6DB00-0CA0 in a SIL 3 safety design?
The module can achieve SIL 3 within an appropriately configured and validated safety application.
Which coding element prevents incorrect replacement of 6ES7136-6DB00-0CA0?
Modulus utitulat electronicum codificationis automaticum typi F.