Siemens 6ES7122-1BB10-0AA0 SIMATIC ET 200L-SC 2DO 24 V DC 2 A Moduli Electronici
Fabricator: Siemens
Condición: Nuevo
Plazo de Entrega: En Stock
Origo: Germania
Garantía: 12 Meses
Inscriptio electronica: [email protected]
whatsapp: +86-18150117685
- Conspectus
- Hot Selling Models
- Producta commendata
Conspectus
- Utere basi TB 16SC vel TB 16IM-SC compatibili.
- Verifica polaritatem inter onus et fontem antequam commutator in locum ponatur.
- Applica limites separatim pro singulis canalibus et pro tota corrente.
- Admitte impulsum ex egressu quando L+ mechanicaliter commutatur et pro mensuris recuperationis contra curtum circuitum declaratis.
6ES7122-1BB10-0AA0 SIMATIC ET 200L-SC 2DO 24 V DC 2 A Electronic Module
A narrow Smart Connect output module with two 24 V DC channels, nominal 2 A output current and electronic short-circuit protection.
Ad Primum Aspectum
| Nota | Siemens |
|---|---|
| Modellum | 6ES7122-1BB10-0AA0 |
| Typus Producti | SC digital-output electronic module |
| Functio principalis | Switching DC field loads |
| Applicatio | Stationes ET 200L-SC et ET 200L-SC IM-SC |
Two DC channels
The module switches two loads with a nominal 2 A channel rating.
Smart Connect base
Installation uses a compatible TB 16SC or TB 16IM-SC terminal block.
Protectio oneris
Electronic output protection limits short-circuit current.
Product Overview
6ES7122-1BB10-0AA0 provides two DC output channels in an ET 200L Smart Connect installation. It plugs into the compatible terminal block and receives its load supply through the base.
The module has green channel-status LEDs, electronic output short-circuit protection and no diagnostic or interrupt function. Output loading must respect both the temperature-dependent channel range and the module total-current limit.
Key Functions
Switch DC actuators
The two channels provide a nominal 2 A output at a rated 24 V DC load supply.
Indicate channel status
A green LED is provided for each output channel.
Limit an output short circuit
Electronic protection acts on the output, with a defined recovery procedure needed after some full-load faults.
Official Specifications
| Emissiones Digitales | 2 |
|---|---|
| Alimentatio oneris nominalis | 24 V DC |
| Nominale Exitus Current | 2 A per canalium |
| Permissible signal-1 current | 5 mA–2,4 A ad 0–40 °C; 5 mA–1,8 A ad 40–60 °C |
| Summa maximalis output moduli | 3 A usque ad 40 °C; 2 A usque ad 60 °C |
| Minimum voltatio output signi-1 | L+ minus 0.5 V |
| Maxima Residua Currus Exitus Signi-0 | 0,6 mA |
| Retardationes output cum onere resistivo | Ascendens: 200 µs maximum; descendens: 1,3 ms maximum |
| Frequentia Maxima Commutandi | Resistivum: 100 Hz; inductivum: 0,2 Hz ad 1 A aut 0,1 Hz ad 2 A; lampescentia: 1 Hz |
| Maxima onus lampadis | 10 W |
| Intervallo resistentiae oneris | 12 Ω–4,8 kΩ |
| Limis corticis output | 2,8–7,2 A typicum |
| Currentus sine onere ab L+ | 6 mA |
| Perdita de Potentia Typical del Modulo | 0.9 W |
| Longitudo Maxima Cavi | 600 m non scutata; 1000 m scutata |
| Isolatio canalis et bus | Nulla isolatio galvanica inter canales aut inter canales et sc bus |
| Indicatio canalium | Unum LED viride per canallem |
| Numerus insertionum permisso-rum in bloco terminali | 20 maximum |
| Dimensiones Moduli | 10 × 64 × 51 mm (L × A × P) |
| Pondus Approximatum | 15 g |
Quaestiones Frequenter Rogatae
Quae systemata blocorum terminalium recipiunt 6ES7122-1BB10-0AA0?
Modulus in catalogo est pro blocis terminalibus TB 16SC et TB 16IM-SC Smart Connect.
Quae inspectio polaritatis necessaria est antequam 6ES7122-1BB10-0AA0 alimentatur?
Inspecte 1L+/1M et 2L+/2M in bloco terminali, quia inversio polaritatis alimentationis oneris actuatores coniunctos activare potest.
Utrum ambo canales 6ES7122-1BB10-0AA0 continuo 2 A ad 60 °C ferre possunt?
Summa moduli limitatur ad 2 A usque ad 60 °C, et unusquisque canalus etiam intra suum intervallum currentis dependentis a temperatura manere debet.
Cur onus post breve circuitum in 6ES7122-1BB10-0AA0 reinitiare non potest?
Plena rekomenco ne estas garantita post mallonga cirkvito, do ŝanĝu la eligan signalon, interrompu la modulan ŝarĝaligon aŭ provizore malkonektu la ŝarĝon.
Ĉu 6ES7122-1BB10-0AA0 elektrike izolas la du eligojn unu de la alia?
Ne ekzistas galvana izolado inter la kanaloj nek inter la kanaloj kaj la SC-a buso.
Ĉu mi povas uzi 6ES7122-1BB10-0AA0 por generi diagnozajn interrompojn pro eraro en eligo?
La modulo ne havas interrompan nek diagnozan funkcion kaj provizas verdajn kanal-statajn LED-ojn.
Kia transiro povas aperi se mi ŝaltas la L+-alimentadon de 6ES7122-1BB10-0AA0 per mekanika kontakto?
Molestiga eliga impulso povas plilongiĝi de 5 µs je nomita kurento ĝis 100 µs je 10 mA ŝarĝo, uzante 10 V limon.