Siemens SIMATIC S5 6ES5465-4UA13 465 Analog Input Module
Fabricator: Siemens
Condición: Nuevo
Plazo de Entrega: En Stock
Origo: Germania
Garantía: 12 Meses
Inscriptio electronica: [email protected]
whatsapp: +86-18150117685
- Conspectus
- Product Overview
- Key Functions
- Official Specifications
- Quaestiones Frequenter Rogatae
- Compatibility & Ordering Notes
- Hot Selling Models
- Producta commendata
Conspectus
Siemens · SIMATIC S5-135U/155U
6ES5465-4UA13 465 Analog Input Module
Siemens 6ES5465-4UA13 is the SIMATIC S5 465 non-isolated analog input module in compact U design, providing sixteen voltage or current inputs and requiring plug-in measuring-range modules.
Ad Primum Aspectum
| Nota | Siemens |
|---|---|
| Modellum | 6ES5465-4UA13 |
| Typus Producti | SIMATIC S5 analog input module |
| Functio principalis | Converts grouped analog field signals into digital process values for the controller |
| Applicatio vel series compatibiles | SIMATIC S5-135U and S5-155U systems |
Range-Module Inventory
Record the exact 6ES5498-1AAxx measuring-range module fitted to each four-channel group.
Common-Potential Check
Keep sensor reference potentials within the permitted difference because the input circuits are non-isolated.
Ambitus migrationis
Match every signal type, channel count and wiring method to the selected adapter and target input module.
Product Overview
Siemens 6ES5465-4UA13 is the SIMATIC S5 465 non-isolated analog input module in compact U design, providing sixteen voltage or current inputs and requiring plug-in measuring-range modules.
Four plug-in measuring-range modules configure sixteen voltage or current inputs in groups of four. The module can acquire eight Pt100 resistance measurements when fitted and wired for the documented range. Selectable fifty- or sixty-hertz integration settings suppress mains-frequency interference during conversion.
Key Functions
Grouped Multi-Range Acquisition
Four plug-in measuring-range modules configure sixteen voltage or current inputs in groups of four.
Pt100 Measurement Mode
The module can acquire eight Pt100 resistance measurements when fitted and wired for the documented range.
Integratio Frequentiae Lineae
Configurationes integrationis seligibiles ad quinquaginta vel sexaginta hertz interferencem frequentiae retis durante conversione supprimunt.
Official Specifications
| Capacitas Input Tensionis et Currentis | 16 canales |
|---|---|
| Capacitas Mensurae Pt100 | 8 input resistentiae |
| Allocatio Modulorum Intervalli Mensurae | 1 modulus pro 4 canalibus input; maximum 4 moduli |
| Moduli Intervalli Mensurae Supportati | 6ES5498-1AA11, -1AA21, -1AA31, -1AA41, -1AA51, -1AA61 et -1AA71 |
| Intervalla Signorum Disponibilia | +/-50 mV, +/-500 mV, +/-1 V, +/-5 V, +/-10 V, +/-20 mA, 4 ad 20 mA et Pt100 |
| Formatum Valoris Mensi | complementum ad duo 13-bit aut magnitudo 12-bit plus signum |
| Representatio Digitalis Nominalis | +/-2048 unitates; 512 ad 2560 unitates pro 4 ad 20 mA |
| Principium mensurationis | Integrating |
| Conversio Methodus | Conversio Dualis Inclinata Tensionis in Tempus |
| Maxima Differentia Potentialis de Referentia | +/-1 V inter potentialia de referentia sensoris et moduli et inter potentialia de referentia canalium sensorum |
| Supplicatio Dorso et Currus | 5 V DC +/-5%; 150 mA typice |
| Expositio transmitteris duo-filaris | 24 V DC onus supply; 20 mA maximum per transmitter |
| Enable and Wire-Break-Test Connections | 24 V DC; approximately 5 mA for each connection |
| Tempus Integrationis | 20 ms at 50 Hz; 16.67 ms at 60 Hz |
| Encoding Time per Measured Value | 60 ms at 50 Hz; 50 ms at 60 Hz |
| Maximum Acquisition Delay at 50 Hz | Approximately 0.48 s for 8 values or 0.96 s for 16 values |
| Input Impedance by Range | At least 10 Mohm for +/-50 mV, +/-500 mV and Pt100; 90 kohm at +/-1 V; 50 kohm at +/-5 V and +/-10 V; 25 ohm at +/-20 mA; 31.25 ohm at 4 to 20 mA |
| Configurable Wire-Break Diagnostics | Available for ±50 mV, ±500 mV and Pt100 ranges |
| Input Voltage Withstand | ±18 V continuous; 75 V for 1 ms at a 1:20 duty ratio |
| Interference Rejection at 50 or 60 Hz | At least 86 dB common-mode and at least 40 dB differential-mode |
Quaestiones Frequenter Rogatae
How do I plan channel capacity for 6ES5465-4UA13?
Use up to sixteen voltage or current channels, or eight Pt100 resistance inputs in the documented configuration.
Which measuring-range module should I fit to 6ES5465-4UA13?
Selige exacte 6ES5498-1AAxx modulum pro desiderato signali intervallo, cum unum intervallo modulum serviat singulis quattuor intratis.
Num possum coniungere duo-filares 4 ad 20 mA transmittentes ad 6ES5465-4UA13?
Ita, utere specificata dispositione duo-filari intervallo cum 24-voltis oneris subministratione et non plus quam 20 milliamperes per transmittentem.
Quomodo debeo administrare referentias potentiales dum 6ES5465-4UA13 conecto?
Serva differentiam inter sensoris et moduli referentias et inter channelis sensoris referentias intra plus vel minus unum volt.
Quam scan delay debet concedi pro 6ES5465-4UA13 ad 50 Hz?
Concede circa 0.48 secundas pro octo valoribus aut 0.96 secundas pro sedecim valoribus ad quinquaginta-hertz configuratione.
Quando possum activare wire-break monitoring in 6ES5465-4UA13?
Wire-break diagnostics configurari possunt pro plus vel minus 50-millivolt, plus vel minus 500-millivolt, et Pt100 intervallo.
Num possum 6ES5465-4UA13 directe substituere uno S7 analogo modulo?
Neniu direktaj sukcesoroj estas specifitaj, do elektu la migradan adaptilon kaj la celan enigan hardvaron por la instalitaj gamoj, la kablometodon kaj la postulatan kanalnombron.
Compatibility & Ordering Notes
Index Compatibilitatis
- Uzu unu konforman mezur-gamomodulon 6ES5498-1AAxx por ĉiu kvar-kanala grupo kaj kontrolu ĉiujn kvar instalitajn poziciojn.
- Konservu ĉiujn diferencojn de sensora referenca potencialo ene de plus aŭ minus unu volto, ĉar la analogaj eniroj ne estas izolitaj.
- Por Pt100-serviĉo, konservu la dokumentitan ok-enigan kablometodon kaj la limigojn kiuj aplikiĝas al la supra kanalgrupo.
- Traktu Siemens S7 adaptilo-kombinojn kiel migradvojojn anstataŭ kiel enŝoveblajn rektajn anstataŭigojn.