Siemens 6EP1961-2BA41 SITOP PSE200U Modulus selectivitatis quattuor canalium 3–10 A
Fabricator: Siemens
Condición: Nuevo
Plazo de Entrega: En Stock
Origo: Germania
Garantía: 12 Meses
Inscriptio electronica: [email protected]
whatsapp: +86-18150117685
- Conspectus
- Hot Selling Models
- Producta commendata
Conspectus
- Dimensio fontis DC regulati pro summa onerum ramorum et onerum initiandi.
- Constitue singulum limitem pro ramo coniuncto et eius conductura.
- Configura ordinem initiandi antequam committantur onera altae inrusionis.
- Permitte 50 mm supra et infra modulum montatum in raediculo DIN et praebeto iustam aestimationem aditus status.
6EP1961-2BA41 SITOP PSE200U 4-Channel 3–10 A Selectivity Module
Modulus electronicus selectivitatis quattuor canalium pro corrente continua, cum limitibus activationis singulis regolabilibus et significatione status per canalem unum.
Ad Primum Aspectum
| Nota | Siemens |
|---|---|
| Modellum | 6EP1961-2BA41 |
| Typus Producti | Modulus electronicus selectivitatis |
| Functio principalis | Protectio selectiva ramorum correntis continuae |
| Applicatio | Circuitus distributionis industrialis correntis continuae |
Limites rami independentes
Unusquisque ex quattuor egressibus habet limitem activationis regolabilem inter 3 et 10 A.
Initiatio oneris alternata
Impostationes interruptoris DIP eligunt initiotionem simulaneam vel initiotionem seriatim cum tempore fixo vel optimato pro onere.
Diagnostics per Canalium
LED output tricolores et signum status pulsus/pausa identificant statum cuiusque rami.
Product Overview
6EP1961-2BA41 distribuit supplitium regulatum DC ad quattuor ramos oneris selecte monitoratos.
Limina rami adiustabilia, ordinatio initiotionis configurabilis et exsulsignum status pulsus/pausa suffragantur initiotionem coordinatam oneris et diagnostica controlleris.
Key Functions
Limites rami independentes
Unusquisque ex quattuor egressibus habet limitem activationis regolabilem inter 3 et 10 A.
Initiatio oneris alternata
Impostationes interruptoris DIP eligunt initiotionem simulaneam vel initiotionem seriatim cum tempore fixo vel optimato pro onere.
Diagnostics per Canalium
LED output tricolores et signum status pulsus/pausa identificant statum cuiusque rami.
Official Specifications
| DC ingress | 24 V nominalis; 22–30 V intervallo |
|---|---|
| Evaluatus Input Correntia | 40 A |
| Protected outputs | 4 canales, 10 A singuli usque ad +60 °C |
| Limen de interrumpere regulabile | 3–10 A per exsul via potentiometro |
| Decrementum voltatis exsurgentis | Approximative 0.2 V infra intritum |
| Ordo initii | Simul vel successive; mora 25 ms, 100 ms aut ad onus optima |
| Trip moderatus pro supercurrente | Circa 5 s ad 1,0–1,5× currentem constitutam |
| Trip pro limitando currente | Typice 100 ms ad 1,5× currentem constitutam |
| Trip celeris | Circa 0,5 ms cum input cadit infra 20 V et output excedit currentem constitutam |
| Currentis residuum post intermissionem | Typice 1 mA |
| Reinitiatio remota | 24 V non-isolated input; high signal above 15 V |
| Exitus Status | Pulse/pause signal for individual-output status evaluation |
| Typical efficiency and dissipation | 99% efficiency; 10 W dissipation at rated load |
| Protection | IP20; Classis III |
| Ambiens Operativa | −25 ad +60 °C cum convectione naturali |
| Dimensiones | 72 × 80 × 72 mm (W × H × D) |
| Ponderis netum | 0.2 KG |
Quaestiones Frequenter Rogatae
Can I set different trip currents on the four branches of 6EP1961-2BA41?
Each output has its own potentiometer for a threshold between 3 A and 10 A.
Can I parallel two outputs of 6EP1961-2BA41 to supply a larger load?
Parallel connection of the protected outputs is not supported.
Quomodo 6EP1961-2BA41 inrusionem simulaneam ex pluribus oneribus minuere potest?
Configuratio initianda eius outputus successive activare potest cum mora 25 ms, 100 ms aut mora ad onus optimizata.
Quid LED flava outputus in 6EP1961-2BA41 significat?
LED flava outputum identificat quod manu est exactivatum.
Quomodo 6EP1961-2BA41 statum singulorum outputuum ad controllorem nuntiat?
Outputus status signum pulsus/pausa utitur quod per SIMATIC functionis blocum aestimari potest.
Quale signum ad remotam repositionem 6EP1961-2BA41 necessarium est?
Inputus remotae repositionis non-isolatus signum altum supra 15 V agnoscit.
Num outputus per 6EP1961-2BA41 exactivatus isolationem galvanicam praebet?
Exactivatio outputus non eum ab inputu electrico isolat.