Siemens 6EP1332-1SH43 LOGO!Power 24 V 2.5 A Fonte de Alimentation
Fabricator: Siemens
Condición: Nuevo
Plazo de Entrega: En Stock
Origo: Germania
Garantía: 12 Meses
Inscriptio electronica: [email protected]
whatsapp: +86-18150117685
- Conspectus
- Hot Selling Models
- Producta commendata
Conspectus
- Calculate the complete 24 V load and temperature-dependent available current.
- Match the AC or DC input and select suitable upstream protection.
- Snap the unit onto the specified 35 mm DIN rail and preserve 20 mm ventilation spacing above and below.
- Use the screw-terminal conductor sizes and any parallel arrangement appropriate to the installation.
6EP1332-1SH43 LOGO!Power 24 V 2.5 A Fonte de Alimentation
fonte de Alimentation LOGO! de 60 W cum inpute AC/DC lato, outpute regulabile de 22.2–26.4 V et corrente nominal de 2.5 A.
Ad Primum Aspectum
| Nota | Siemens |
|---|---|
| Modellum | 6EP1332-1SH43 |
| Typus Producti | Stabilized DC power supply |
| Functio principalis | Conversione de inpute AC vel DC ad DC regulatum |
| Applicatio | cargas de controllo et automatione a 24 V |
Intratio Tensionis Latae
Hoc apparatu accipit inpute AC monofasico vel DC intra limites operative declaratos.
Adjustable regulated output
Un potentiometrum regit tensionem nominalem 24 V DC inter 22.2 et 26.4 V.
Supplicium oneris DC protectum
Protectio contra curtum circuitum ad currentem constantem et LED viridis 'output OK' ad operationem et servitium favent.
Product Overview
6EP1332-1SH43 supplicium regulatum et isolatum 24 V DC ad currentem nominalem 2.5 A pro instrumentis de controllo.
Supplicium potentiae in rastrum DIN accipit latam intrationem AC vel DC et coniungit protectionem contra curtum circuitum ad currentem constantem, indicationem tensionis exirentis et refrigerationem per convectionem naturalem.
Key Functions
Intratio Tensionis Latae
Hoc apparatu accipit inpute AC monofasico vel DC intra limites operative declaratos.
Adjustable regulated output
Un potentiometrum regit tensionem nominalem 24 V DC inter 22.2 et 26.4 V.
Supplicium oneris DC protectum
Protectio contra curtum circuitum ad currentem constantem et LED viridis 'output OK' ad operationem et servitium favent.
Official Specifications
| AC Input | 100–240 V AC nominalis; ambitus operativus 85–264 V |
|---|---|
| DC ingress | 110–300 V DC |
| Input frequency | 47–63 Hz |
| Evaluatus Input Correntia | 1.22 A ad 120 V; 0.66 A ad 230 V |
| Maxima Currus Inrumpens | 46 A ad 25°C |
| Custodia Rete Electrici | Al minus 40 ms ad inputo de 187 V e currente nominal in outputo |
| Classificatus exitus | 24 V CC; 2,5 A; 60 W |
| Regulatio Output | 22.2–26.4 V DC per potentiometrum |
| Diminutio currentis exsistentis | 2% per K ab +55 usque ad +70°C |
| Maxima fluctuatio outputus | 200 mV |
| Maxima tensio outputus | 300 mV |
| Efficientia et damnum | 88%; 8 W typice ad outputum nominalem |
| Consumptio sine onere | 1.8 W maxime |
| Characteristicum curtocircuitus | Current constans; 3.3 A typice |
| Operatio Parallelis | Usque ad 2 unitates pro aucta potentia outputus |
| Tutela Electrica | Classis II; tensio isolata salutifera minima |
| Temperatura operativa | −20 ad +70°C cum convectione naturali |
| Temperatura servandi et transportandi | −40 ad +85°C |
| Installatio | IP20; railem DIN 35 mm; spatium 20 mm supra et infra |
| Dimensiones et pondus corporis | 72 × 90 × 52.6 mm (latus × altitudo × profunditas); 0.25 kg |
Quaestiones Frequenter Rogatae
Num possum 6EP1332-1SH43 ex fonte CC, non ex reti CA, excitare?
Hoc instrumentum accipit ingressum CC inter 110 et 300 V.
Quousque potest variari exitus 6EP1332-1SH43?
Potentiometrum exitus dat intervallum variationis 22.2–26.4 V CC.
Num 6EP1332-1SH43 potest dare suum integrum 2.5 A ad +70°C?
The output must be derated by 2% per kelvin above +55°C.
How much vertical clearance must I leave around 6EP1332-1SH43?
Leave 20 mm above and 20 mm below the power supply.
Can I connect two units of 6EP1332-1SH43 in parallel for a larger load?
The specified parallel arrangement permits up to two units for increased output power.
Does 6EP1332-1SH43 need a protective-earth conductor?
The Class II power supply operates without a protective conductor.
What happens when the output of 6EP1332-1SH43 is shorted?
The short-circuit-proof output follows a constant-current characteristic with a typical current of 3.3 A.