Siemens SIMATIC ET 200SP HA AQ 8xI HART Analog Output Module 6DL1135-6TF00-0PH1
Fabricator: Siemens
Condición: Nuevo
Plazo de Entrega: En Stock
Origo: Germania
Garantía: 12 Meses
Inscriptio electronica: [email protected]
whatsapp: +86-18150117685
- Conspectus
- Product Overview
- Key Functions
- Official Specifications
- Quaestiones Frequenter Rogatae
- Compatibility & Ordering Notes
- Hot Selling Models
- Producta commendata
Conspectus
SIEMENS · SIMATIC ET 200SP HA
6DL1135-6TF00-0PH1 SIMATIC ET 200SP HA AQ 8xI HART Analog Output Module
The ET 200SP HA AQ 8xI HART module provides eight precision current outputs with HART communication, channel diagnostics, 16-bit representation, and redundant operation on an M1 terminal block.
Ad Primum Aspectum
| Nota | Siemens |
|---|---|
| Modellum | 6DL1135-6TF00-0PH1 |
| Typus Producti | Eight-channel HART analog current output module |
| Functio principalis | Outputs precision current signals and exchanges HART data with field actuators |
| Applicatio vel series compatibiles | SIMATIC PCS 7 ET 200SP HA stations using H1 or M1 terminal blocks |
Identificatio exacta.
Match 6DL1135-6TF00-0PH1 character by character and confirm the complete SIMATIC ET 200SP HA AQ 8xI HART Analog Output Module designation.
Arrangementum Interfacis
Confirmare ante connexionem substitutionis supplitum installatum, portus, connexiones campestres et accessoria requisa.
Configuration Check
Servare projectum ingenieriae approbatum, parametres rete et data applicationis quae systema installatum utitur.
Product Overview
The ET 200SP HA AQ 8xI HART module provides eight precision current outputs with HART communication, channel diagnostics, 16-bit representation, and redundant operation on an M1 terminal block.
Eight channels provide analog current control with HART communication to compatible field devices. M1 terminal-block installation supports redundant module operation with a maximum 20 ms failover. Per-channel wire-break, short-circuit, and range diagnostics support plant maintenance.
Key Functions
Octo HART Current Outputs
Octo canales praebent analogum currentem controllem cum HART communicatione ad compatibiles dispositivos in campo.
Operatio Altius-Disponibilitatis
M1 terminal-block installationem suadet redundantem modulum operationem cum maximo 20 ms failover.
Diagnostics Canalium
Per-canalem wire-break, short-circuit et range diagnostics suadent plantam maintenance.
Official Specifications
| Egressus Analogici | 8 current channels |
|---|---|
| Intervalla output | 0–10 mA, 0–20 mA et 4–20 mA |
| representatio 4–20 mA | 16 bit inclusu signo |
| Accuratio basica ad 25 °C | ±0.1% |
| Maxima Resistentia Onus | 750 Ω |
| Maximum Inductivum Onus | 10 mH |
| Maxima Longitudo Cavi Scutati | 1000 m |
| Tensio nominalis supplicii | 24 V DC |
| Permissum Supplicationis Intervallum | 19,2 ad 28,8 V CC |
| Perditio potentiæ typica | 3.2 W |
| Terminales coniunctionis | H1 and M1 |
| Redundantia | Supportatus cum blocco terminali M1 |
| Maximum Redundancy Failover Time | 20 ms |
| Temperatura operationis, horizontalis | −40 ad +70 °C |
| Dimensiones | 22.5 x 115 x 138 mm |
| Pondus Approximatum | 160 g |
Quaestiones Frequenter Rogatae
Quae current ranges configurari possunt in 6DL1135-6TF00-0PH1?
Utere 0 ad 10 mA, 0 ad 20 mA aut 4 ad 20 mA secundum connectum actuatorem.
Potestne 6DL1135-6TF00-0PH1 communicare cum dispositivis HART in campo?
Ita; quaelibet canal analogus currentis suum functio communicationis HART documentatam subtenet.
Quod tabulatum terminalium permittit redundantiam pro 6DL1135-6TF00-0PH1?
Utere tabulato terminalium M1 pro disposito ordine moduli redundantis.
Quid est maximum tempus transitus ad redundans pro 6DL1135-6TF00-0PH1?
Tempus transitus maximum specificatum est 20 ms in ordine redundantis sine errore.
Quae defectus canalis 6DL1135-6TF00-0PH1 diagnosticare potest?
Modulus detegit interruptionem fili, cortocircuitum, et effusionem aut subflusionem per singulum canalem.
Quam longa esse potest cassida actuatoris pro 6DL1135-6TF00-0PH1?
The specified maximum shielded cable length is 1000 metres.
Quid servandum est antequam 6DL1135-6TF00-0PH1 substituitur?
Registra le gamme dei canali, i parametri HART, i valori sostitutivi, le diagnostiche, il blocco terminali e l'assegnazione della ridondanza.
Compatibility & Ordering Notes
Index Compatibilitatis
- Usa blocchi terminali H1 o M1 e scegli M1 quando è richiesto l'assetto ridondante documentato.
- Conferma che ogni carico attuatore rimanga entro i limiti specificati di impedenza in uscita di corrente e di cavo.
- Preserva le variabili HART, le diagnostiche e i valori sostitutivi prima di sostituire il modulo.