Siemens 3RN2010-1CA30 SIRIUS 3RN2 Relais de protection moteur à thermistance
Fabricator: Siemens
Condición: Nuevo
Plazo de Entrega: En Stock
Origo: Germania
Garantía: 12 Meses
Inscriptio electronica: [email protected]
whatsapp: +86-18150117685
- Conspectus
- Hot Selling Models
- Producta commendata
Conspectus
- Praebere 24 V AC ad 50/60 Hz aut 24 V DC intra ambitum permisum alimentationis.
- Design the control sequence for automatic reset rather than manual or remote reset.
- Keep contact loads within the relevant AC-15 or DC-13 rating.
- Tighten screw terminals to 0.6–0.8 N·m and use the specified conductor sizes.
3RN2010-1CA30 SIRIUS 3RN2 Thermistor Motor Protection Relay
A compact 17.5 mm evaluation relay with 24 V AC/DC supply, automatic reset and separate NO and NC contacts.
Ad Primum Aspectum
| Nota | Siemens |
|---|---|
| Modellum | 3RN2010-1CA30 |
| Typus Producti | Motor temperature protection relay |
| Functio principalis | Evaluating thermal sensor signals |
| Applicatio | Motor winding temperature supervision |
Evaluate temperature sensors
The compact evaluation unit provides thermistor motor protection and is suitable for bimetallic switches.
Indicate the protection state
Two LEDs show ready and tripped conditions.
Integrate into the control circuit
One normally open contact and one normally closed contact provide relay outputs.
Product Overview
3RN2010-1CA30 evaluates motor-temperature sensing circuits in a compact SIRIUS 3RN2 housing.
The automatic-reset design is also suitable for a bimetallic switch and provides separate ready and tripped indications for local supervision.
Key Functions
Evaluate temperature sensors
The compact evaluation unit provides thermistor motor protection and is suitable for bimetallic switches.
Indicate the protection state
Two LEDs show ready and tripped conditions.
Integrate into the control circuit
One normally open contact and one normally closed contact provide relay outputs.
Official Specifications
| Control Supply | 24 V AC a 50/60 Hz o 24 V DC |
|---|---|
| Factor Operativus Supplicationis | 0.85–1.10 times rated voltage |
| Reset Arrangement | Reset automaticus; nullus reset manualis aut externus |
| Contactus Exirentes | 1 NO et 1 NC; materiale contactuum AgSnO₂ |
| Classis contactuum AC-15 | 3 A ad 250 V AC |
| Classis contactuum DC-13 | 1 A ad 24 V DC; 0,2 A ad 125 V DC; 0,1 A ad 250 V DC |
| Maxima currentis thermicae per contactus | 5 A |
| Perditio potentiæ typica | 0.4 W |
| Buffering supplitus | Minime 40 ms |
| Tensionis insulatio evaluata | 300 V, categoria superensionis III et gradus pollutionis 3 |
| Tensio Impulsus Tolerata | 4 kV |
| Mecanicus Patiens | 10 milioane de cicluri de funcționare tipice |
| Terminalis genus | Terminalia a vitiis avulsibilia |
| Sectio Transversa Conductoris | Conductor solidus unus aut fasciculatus, finissime intortus: 0.5–4 mm² |
| Par de torsion pro terminalibus | 0,6–0,8 N·m |
| Montatio | Fixatio per vitam aut per adhaesionem in rilu DIN 35 mm; quavis positione |
| Temperatura operativa | −25 usque ad +60 °C |
| Altitudo Installationis Maxima | 2,000 m |
| Dimensiones (L × H × D) | 17.5 × 100 × 90 mm |
| Ponderis netum | 104.46 g |
Quaestiones Frequenter Rogatae
Num 3RN2010-1CA30 manuale restitutio post interruptionem postulat?
Haec compendiosa unitas aequationis automaticam restitutionem utitur et nullam functionem manuale restitutio habet.
Num interruptor temperaturae bimetallicus per 3RN2010-1CA30 aequari potest?
Hoc relais aptum est ad usum cum interruptore bimetallico et cum protectione motoris thermistorica.
Num 3RN2010-1CA30 directe ab circuitu controlis 230 V AC alere possum?
Suppeditatio controlis requiritur: 24 V AC aut 24 V DC.
Potestne pulsator remotus ad 3RN2010-1CA30 connecti esse?
Functionem externi reinitiationis haec versio automaticae reinitiationis non praebet.
Quae indicationes locales statum 3RN2010-1CA30 identificare iuvant?
Duo LED statum parati et statum trip indicant.
Quomodo 3RN2010-1CA30 tam signa permittentia quam signa trip praebere potest?
Dispositio output unum contactum normaliter apertum et unum contactum normaliter clausum praebet.
Possuntne terminales de controllo a 3RN2010-1CA30 removi pro servitio?
Circuitus auxiliarius et circuitus de controllo terminalibus vitandis per vitem utuntur.