Conspectus
- Provide coordinated feeder short-circuit protection separately.
- Set electronic overload protection to suit the connected motor and application.
- Use the specified DC control supply and observe the absence of reverse-polarity protection.
- Maintain the required clearances and account for derating with alternative mounting positions.
3RM1002-1AA04 SIRIUS 3RM1 0.4–2 A Direct Motor Starter
A narrow hybrid direct starter with electronic overload protection, 24 V DC control and screw terminals.
Ad Primum Aspectum
| Nota | Siemens |
|---|---|
| Modellum | 3RM1002-1AA04 |
| Typus Producti | Direct-on-line motor starter |
| Functio principalis | Motor switching and overload protection |
| Applicatio | Small three-phase motor feeders |
Protectio Electronica Regulabilis
The current-dependent overload release is adjustable from 0.4 A to 2 A.
Hybrid direct switching
Three hybrid-switched poles start a motor in one direction.
Hardwired control and indication
Starter usat signales de control 24 V DC et dat indication electronic de functionamento plus contactu de commutation auxiliar.
Product Overview
3RM1002-1AA04 combina initiation directe de motor con liberation electronic de supercarga ajustabil.
Su circuitu de commutation hybrid tractat tres polos principal in un carcassa de latore 22.5 mm, con output de status et contactu de commutation auxiliar pro control de machina.
Key Functions
Protectio Electronica Regulabilis
The current-dependent overload release is adjustable from 0.4 A to 2 A.
Hybrid direct switching
Three hybrid-switched poles start a motor in one direction.
Hardwired control and indication
Starter usat signales de control 24 V DC et dat indication electronic de functionamento plus contactu de commutation auxiliar.
Official Specifications
| Tensione principal de operation | 48–500 V AC; 50/60 Hz |
|---|---|
| Regulatione de currente de supercarga | 0.4–2 A |
| Currente nominal del circuito principal | 2 A ad 400 V |
| Potentia motoris ad 400 V, 50 Hz | 0,09–0,75 kW |
| Maximus cursus initiatus | 16 A |
| Circulus interruptoris principalis | 3 poli cum contactibus interruptoribus hybridis |
| Control Supply | nominalis 24 V DC; intervallo 19,2–30 V |
| Current input controlis digitalis | 11 mA ad signum 1; 1 mA ad signum 0 |
| Output signalisationis electronicae | 24 V DC, 15 mA |
| Contactus auxiliaris | 1 commutatio; maximum 3 A ad AC-15/230 V vel 1 A ad DC-13/24 V |
| Ritardos de commutatione | 60–90 ms pro utramque operationem, activationem et deactivationem |
| Frequentia Maxima Commutandi | 1 operatio per secundum |
| Terminal arrangement | Terminales cum vitiis pro circuitibus principalibus et de regula |
| Maximum Unshielded Motor Cable | 100 m |
| Protection | IP20 in parte anteriori; tutum ad digitos |
| Ambiens Operativa | −25 usque ad +60 °C |
| Dimensiones | 22.5 × 100 × 141.6 mm (latitudo × altitudo × profunditas) |
| Ponderis netum | 0.274 kg |
Quaestiones Frequenter Rogatae
Num 3RM1002-1AA04 vertere potest directionem motoris?
Hic initiator directus in lineam unam directionem praebet et non praebet initiationem inversam.
Num regula supercarii 3RM1002-1AA04 ad motorem 1 A adaptari potest?
The adjustable overload-release range covers motor currents from 0.4 A to 2 A.
Does 3RM1002-1AA04 replace the feeder short-circuit protective device?
The starter does not provide short-circuit protection.
Can I use 3RM1002-1AA04 as a safety-rated emergency-stop device?
This version is not suitable for safety-related switching.
How much top and bottom clearance does 3RM1002-1AA04 need in a row?
Allow 50 mm above and 50 mm below the starter.
What main-circuit conductor size can I terminate on 3RM1002-1AA04?
The main contacts accept solid or stranded conductors from 0.5 mm² to 4 mm².
Does 3RM1002-1AA04 connect directly to PROFINET or AS-Interface?
The starter uses hardwired control and has no bus-communication function.