Siemens 3RK1922-2BA00 ET 200pro 110 mm Rear Wall Bus Module
Fabricator: Siemens
Condición: Nuevo
Plazo de Entrega: En Stock
Origo: Germania
Garantía: 12 Meses
Inscriptio electronica: [email protected]
whatsapp: +86-18150117685
- Conspectus
- Hot Selling Models
- Producta commendata
Conspectus
- Use the 2BA01 base for a Safety Local repair switch.
- Seat the rear wall seals correctly before joining adjacent modules.
- Tighten the mounting bolts to 1.5 Nm.
- Fit the station terminating module and seal unused front connections as required by the station arrangement.
3RK1922-2BA00 ET 200pro 110 mm Rear Wall Bus Module
A rear wall base that carries the data bus and 24 V supply paths for ET 200pro motor starters and special modules.
Ad Primum Aspectum
| Nota | Siemens |
|---|---|
| Modellum | 3RK1922-2BA00 |
| Typus Producti | Plug-in backplane base |
| Functio principalis | Connecting modular starter assemblies to the station bus |
| Applicatio | ET 200pro special modules and motor starters |
Separate supply paths
Basis transfert elektro-nika/sensoria 1L+ et supplitio oneris 2L+.
Data et controllo
Bus dati et voltatio actuationis ASM-400V transibunt per modulum parietis posterioris.
Confectio stationis hermetica
Sedes correcta sigillorum et confectionis essentialis est pro gradu protectionis installato.
Product Overview
3RK1922-2BA00 praebet connexionem bus parietis posterioris pro modulo speciali ET 200pro vel initiatore motoris. Connexiones in plagulam portant bus dati stationis, supplitio elektro-nika/sensoria, supplitio oneris et voltatio controllo pro modulo clausurae ASM-400V.
Modulus 110 mm convenit portatori latiori initiatoris motoris et coniungitur cum modulis parietis posterioris adiacentibus. Protectio frontalis sua propria et protectio stationis correcte confectae differunt, ideo sigilla, fixatores et modulus frontalis aptatus sunt partes dispositio installationis.
Key Functions
Porta buses supplitii auxiliaris
Basis transfert 24 V electronica/sensor et vias de alimentatio oneris per stationem initiatoriam.
Serva communicationem stationis
Connesiones insertiles portant omnibus datos et tensionem actuationis ASM-400V.
Sustine modulum anteriorem amovibilem
Retentores et contactus insertiles praebent connexionem montionis pro modulo initiatorio vel speciali assignato.
Official Specifications
| Tensio nominata barrae bus | 24 V DC pro 1L+ et 2L+ |
|---|---|
| Capacitas Currentus Busbar | 10 A |
| Allocatio viae alimentationis | 1L+: alimentatio electronicae/sensoris; 2L+: alimentatio oneris |
| Translatio Signali | Omnibus data et tensio actuationis ASM-400V |
| Electrica connectio | Conexio plug |
| Dispositivo de protectione | IP00 in fronte independent; IP65 post installation correcte |
| Anterioris contactus protectio | Securo contra digitos secundum IEC 60529 |
| Temperatura operativa | −25 ad +55 °C |
| Temperatura servandae | −40 usque ad +70 °C |
| Largor nominal de installation | 110 mm |
| Ponderis netum | 241 g |
Quaestiones Frequenter Rogatae
Poteo io montar un interruptor de reparation local de securitate super le 3RK1922-2BA00?
Le interruptor de reparation local de securitate require le modulo de bus de pariete posterior codificate separatemente que termina in 2BA01.
Quid inspicere debes antequam 3RK1922-2BA00 in vehiculo coniungitur?
Verifica ut sigilla recte collocata sint antequam modulum parietis posterioris in locum coniungas.
Num 3RK1922-2BA00 tantum subministrationem electronicam portat?
Basis utramque subministrationem, electronicam/sensoriam et subministrationem oneris, transfert.
Quanta currentia a barris omnibus 3RK1922-2BA00 portari potest?
Capacitas nominata barri omnium ad currentiam ferendam est 10 A.
Num 3RK1922-2BA00 expositus solus gradum protectionis stationis installatae praebet?
Frons isolata est IP00; gradus IP65 requirit installationem rectam.
Quae torque adstringendi usus est cum 3RK1922-2BA00 in statione firmatur?
Bolts moduli parietis posterioris Phillips adstringe ad 1.5 Nm.
Can I remove a motor starter fitted to 3RK1922-2BA00 while its feeder remains energized?
De-energize the feeder before removing the motor starter from the rear wall base.