IC200ALG260G VersaMax Eight-Channel Analog Input Module
An eight-channel single-ended input module with 12-bit conversion, carrier-jumper range selection and backplane-powered electronics.
Ad Primum Aspectum
| Nota | GE Fanuc |
|---|---|
| Modellum | IC200ALG260G |
| Typus Producti | Modulus Ingressus Analogicus |
| Functio principalis | Acquiring voltage or current measurements |
| Applicatio | VersaMax CPU and network-interface I/O stations |
Hardware-selected signal ranges
Carrier jumpers select current operation or bipolar and unipolar voltage operation.
Eight-word data interface
The module supplies eight words of analog input data to the CPU or network interface.
Separate power indicators
INT PWR and OK indicators distinguish internal field-circuit power from backplane power.
Product Overview
IC200ALG260G acquires eight analog field signals through the VersaMax I/O system.
All inputs share a common return, while optical isolation separates the field-input group from logic and frame ground; external power remains necessary for the connected transmitters.
Key Functions
Hardware-selected signal ranges
Carrier jumpers select current operation or bipolar and unipolar voltage operation.
Eight-word data interface
The module supplies eight words of analog input data to the CPU or network interface.
Separate power indicators
INT PWR and OK indicators distinguish internal field-circuit power from backplane power.
Official Specifications
| Input arrangement | 8 single-ended channels in one group |
|---|---|
| Intervalla Signorum | ±10 V DC default; configurable 0–10 V DC or 4–20 mA |
| Resolutio Conversionis | 12 bits; 2.5 mV or 4 µA increments correspond to 8 reported counts |
| Input-to-logic and frame isolation | 250 V AC continuous; 1,500 V AC for 1 minute |
| Isolatio Canalium | Nulla isolatio inter canales; communis reditus |
| Maxima onus dorsalis | 130 mA ex 5 V |
| Fons Potentiae Moduli | Dorsalis; nulla separata alimentatio moduli |
| Impedantia ingressus tensionis | 126 kΩ maximum |
| Impedantia ingressus currentis | 200 Ω maximē |
| Accuratio ad 25 °C | +/-0.3% valoris pleni typice; +/-0.5% maximum |
| Accuratio super 0–60 °C | +/-1% valoris pleni maximum; potest deteriorari ad +/-3% sub gravi interfectione RF 10 V/m |
| Responsio filtrorum intrantium | 5 ms |
| Cursus Actualizationis Moduli | 0.4 ms |
| Minima reiectio crosstalk canalis | 30 dB |
| Allocatio datarum | 8 verba analogica intrantis |
| Diagnostica moduli | Amisso potestate interna pro circuitibus lateris campi |
Quaestiones Frequenter Rogatae
Num canales intrantes IC200ALG260G singillatim isolati sunt?
Intrantes communem reditum habent et ab invicem non isolantur.
Quomodo operationem in voltibus vel in currentibus in IC200ALG260G seligo?
Utere duobus iuncturis in terminalibus portatoris ad modum operationis et ambitum voltuum seligendum.
Which range does IC200ALG260G use when no selection jumper is fitted?
With no jumper installed, the module accepts bipolar −10 to +10 V DC signals.
Can IC200ALG260G supply power to the field transmitters?
An external source must provide power for the field transmitters.
Can I connect both voltage and current devices to the same channel on IC200ALG260G?
Connect either a voltage device or a current device to a channel, rather than both.
Does the 0.4 ms update rate of IC200ALG260G remove the input-filter delay?
The module has a specified 5 ms input-filter response in addition to its 0.4 ms update rate.
What do the two green power indicators on IC200ALG260G mean?
INT PWR indicates internal field-circuit power and OK indicates backplane power.