Siemens SIMATIC ET 200iSP 4 F-AI Ex HART Electronic Module 6ES7138-7FA00-0AB0
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Product Overview
- Key Functions
- Official Specifications
- Frequently Asked Questions
- Compatibility & Ordering Notes
- Hot Selling Models
- Recommended Products
Overview
SIEMENS · SIMATIC ET 200iSP
6ES7138-7FA00-0AB0 SIMATIC ET 200iSP 4 F-AI Ex HART Electronic Module
The 4 F-AI Ex HART module is a fail-safe SIMATIC ET 200iSP electronic module with four intrinsically safe analog inputs for HART two-wire transmitters.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7138-7FA00-0AB0 |
| Product Type | Fail-safe intrinsically safe analog input electronic module |
| Core Function | Acquires HART current signals in safety-related hazardous-area applications |
| Application or Compatible Series | SIMATIC ET 200iSP distributed I/O stations |
Exact Identification
Match 6ES7138-7FA00-0AB0 character by character and confirm the complete SIMATIC ET 200iSP 4 F-AI Ex HART Electronic Module designation.
Interface Arrangement
Confirm the installed supply, ports, field connections and required accessories before wiring the replacement.
Configuration Check
Preserve the approved engineering project, network parameters and application data used by the installed system.
Product Overview
The 4 F-AI Ex HART module is a fail-safe SIMATIC ET 200iSP electronic module with four intrinsically safe analog inputs for HART two-wire transmitters.
Four safety-related analog channels support process measurements in hazardous-area installations. The input channels support HART communication with compatible two-wire transmitters. The module is specified for applications up to SIL 3, PL e and Category 4 when used in an approved configuration.
Key Functions
Fail-Safe Analog Acquisition
Four safety-related analog channels support process measurements in hazardous-area installations.
HART Device Communication
The input channels support HART communication with compatible two-wire transmitters.
High Safety Integrity
The module is specified for applications up to SIL 3, PL e and Category 4 when used in an approved configuration.
Official Specifications
| Product Version | 01 |
|---|---|
| Analog Input Channels | 4 |
| Input Signal Range | 0/4 to 20 mA |
| Transmitter Connection | HART two-wire transmitter |
| HART Protocol Version | 7.0 |
| Functional Safety Level | Up to SIL 3 according to IEC 61508:2010 |
| Performance Level | PL e according to ISO 13849-1:2015 |
| Safety Category | Category 4 according to ISO 13849-1:2015 |
| Gas Ex Classification | Ex ib (ia Ga) IIC T4 Gb |
| Dust Ex Classification | Ex ib [ia IIIC Da] IIC T4 Gb |
| Mining Ex Classification | Ex ib [ia] I Mb |
Frequently Asked Questions
How many process signals can 6ES7138-7FA00-0AB0 acquire?
Four analog current channels are available for safety-related measurement.
Which signal range is supported by 6ES7138-7FA00-0AB0?
The channels support the 0/4 to 20 mA current range.
Can HART two-wire transmitters be connected to 6ES7138-7FA00-0AB0?
Yes; compatible two-wire transmitters can communicate using HART protocol version 7.0.
What safety integrity can 6ES7138-7FA00-0AB0 support?
An approved installation can be engineered for applications up to SIL 3, PL e and Category 4.
Is 6ES7138-7FA00-0AB0 suitable for intrinsically safe circuits?
Yes; it carries gas, dust and mining intrinsic-safety classifications for the specified installation conditions.
What must be checked before wiring 6ES7138-7FA00-0AB0?
Verify the hazardous-area classification, transmitter type, channel parameters, barriers and grounding concept.
What commissioning checks are important for 6ES7138-7FA00-0AB0?
Validate each current loop, HART address, safety parameter set, diagnostic response and proof-test procedure.
Compatibility & Ordering Notes
Compatibility Checklist
- Install the electronic module only in an approved SIMATIC ET 200iSP station configuration.
- Match every connected transmitter and field circuit to the applicable intrinsic-safety parameters.
- Validate the safety program, channel parameters and proof-test procedure before returning the loop to service.