SIEMENS · SIMATIC ET 200SP HA
6DL1134-6TH00-0PH1 SIMATIC ET 200SP HA AI 16xI HART Module
The SIMATIC ET 200SP HA AI 16xI 2-wire HART module provides sixteen current-input channels, 16-bit conversion, channel diagnostics and run-time reparameterization.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6DL1134-6TH00-0PH1 |
| Product Type | sixteen-channel HART analog input module |
| Core Function | Acquires sixteen 2-wire current signals and exchanges HART data |
| Application or Compatible Series | ET 200SP HA process I/O stations using current transmitters with HART |
Exact Identification
Match 6DL1134-6TH00-0PH1 character by character and confirm the complete SIMATIC ET 200SP HA AI 16xI HART Module designation.
Interface Arrangement
Confirm the installed supply, ports, field connections and required accessories before wiring the replacement.
Configuration Check
Preserve the approved engineering project, network parameters and application data used by the installed system.
Product Overview
The SIMATIC ET 200SP HA AI 16xI 2-wire HART module provides sixteen current-input channels, 16-bit conversion, channel diagnostics and run-time reparameterization.
Sixteen two-wire current inputs reduce module count in process I/O stations. HART communication supports compatible intelligent field transmitters. The module is supported by current PCS 7, PCS neo, STEP 7 and GSDML engineering environments.
Key Functions
High Channel Density
Sixteen two-wire current inputs reduce module count in process I/O stations.
Integrated HART
HART communication supports compatible intelligent field transmitters.
HA Engineering Support
The module is supported by current PCS 7, PCS neo, STEP 7 and GSDML engineering environments.
Official Specifications
| Firmware Version | V1.1 |
|---|---|
| Firmware Update | Supported |
| Identification Data | I&M0 to I&M3 |
| TIA Portal Baseline | V16 |
| STEP 7 Baseline | V5.6 |
| PCS 7 Baseline | V9 |
| PCS neo Baseline | V3 |
| GSDML Baseline | V2.3 |
| Module Redundancy | Supported with M1 terminal arrangement |
| Reparameterization in RUN | Supported |
| Rated Supply | 24 V DC |
| Permissible Supply Range | 19.2 to 28.8 V DC |
| Reverse-Polarity Protection | Supported |
| Current Consumption Without Sensors | 80 mA |
| Power Loss | 4.5 W |
| Analog Input Channels | 16 |
| Transmitter Connection | 2-wire current |
| HART Communication | Supported |
| Resolution | 16 bit |
| Basic Accuracy | ±0.1% |
Frequently Asked Questions
How many current-input channels are provided by 6DL1134-6TH00-0PH1?
Sixteen analog input channels are available.
Can 6DL1134-6TH00-0PH1 communicate with HART transmitters?
Yes; HART communication is supported on the current inputs.
Can parameters be changed while 6DL1134-6TH00-0PH1 is running?
Yes; reparameterization during RUN is supported.
Which signal wiring is intended for 6DL1134-6TH00-0PH1?
The module is designed for two-wire current transmitters.
What conversion resolution does 6DL1134-6TH00-0PH1 provide?
The analog values are converted with 16-bit resolution.
Can 6DL1134-6TH00-0PH1 be used in a redundant I/O arrangement?
Yes; module redundancy is supported with the specified M1 terminal arrangement.
What must be saved before replacing 6DL1134-6TH00-0PH1?
Preserve channel parameters, measuring ranges, HART assignments, redundancy settings and the process-control project.
Compatibility & Ordering Notes
Compatibility Checklist
- Match the installed H1, M1, N0, H0 or M0 terminal-block arrangement exactly.
- Back up every channel range, HART address and diagnostic parameter.
- Verify redundancy pairing and the approved PCS 7 or PCS neo hardware configuration.