Siemens 6ES7334-0CE01-0AB0 SIMATIC S7-300 SM 334 Analog IO Module
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Use the signal wiring appropriate to 0–10 V or 0–20 mA operation.
- Use the four-wire transducer arrangement for current measurement.
- Keep voltage and current output loads within the specified impedance limits.
- Fit the 20-pin front connector and account for the non-isolated input arrangement.
6ES7334-0CE01-0AB0 SIMATIC S7-300 SM 334 Analog IO Module
Combined analog module with four inputs, two outputs and 8-bit conversion for voltage and current signals.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7334-0CE01-0AB0 |
| Product Type | Combined analog input/output module |
| Core Function | Analog signal acquisition and actuator command output |
| Application | Compact analog IO in S7-300 control stations |
Combined sensor and actuator signals
Four inputs acquire analog process values while two outputs provide analog commands to connected equipment.
Voltage and current operation
Inputs and outputs support 0–10 V or 0–20 mA signals with wiring appropriate to the selected circuit.
Compact analog conversion
Eight-bit input and output conversion supports straightforward analog tasks in an S7-300 station.
Product Overview
6ES7334-0CE01-0AB0 combines four analog inputs and two analog outputs in a compact S7-300 module.
Voltage and current signal connections support local sensors and actuators, with an eight-bit conversion format and a common 20-pin front wiring connection.
Key Functions
Combined sensor and actuator signals
Four inputs acquire analog process values while two outputs provide analog commands to connected equipment.
Voltage and current operation
Inputs and outputs support 0–10 V or 0–20 mA signals with wiring appropriate to the selected circuit.
Compact analog conversion
Eight-bit input and output conversion supports straightforward analog tasks in an S7-300 station.
Official Specifications
| Analog input channels | 4 |
|---|---|
| Analog output channels | 2 |
| Input and output resolution | 8 bits |
| Rated load supply | 24 V DC |
| Maximum load-supply current | 110 mA without load |
| Maximum backplane current | 55 mA at 5 V DC |
| Typical power loss | 3 W |
| Voltage input range | 0–10 V; 100 kΩ input resistance |
| Current input range | 0–20 mA; 50 Ω input resistance |
| Maximum all-channel input cycle | 5 ms |
| Output signal ranges | 0–10 V or 0–20 mA |
| Minimum voltage-output load | 5 kΩ; maximum 1 µF capacitive load |
| Maximum current-output load | 300 Ω; maximum 1 mH inductive load |
| Output conversion time | 500 µs per channel |
| Output settling time | 0.3 ms resistive/inductive; 3 ms capacitive |
| Maximum shielded cable length | 200 m for inputs and outputs |
| Input isolation from backplane | None |
| Field wiring connection | 20-pin front connector |
| Dimensions (W × H × D) | 40 × 125 × 117 mm |
| Weight | Approximately 285 g |
Frequently Asked Questions
Can 6ES7334-0CE01-0AB0 connect a Pt100 sensor directly?
The supported analog inputs are voltage and current inputs rather than direct resistance thermometer inputs.
Can 6ES7334-0CE01-0AB0 power a two-wire current transmitter through the input?
Its current measurement connection is intended for four-wire transducers and does not provide the two-wire transmitter connection function.
What load can a current output on 6ES7334-0CE01-0AB0 drive?
The maximum load resistance is 300 Ω within the rated current output range.
What impedance should a voltage-output load present to 6ES7334-0CE01-0AB0?
A voltage-output load must be at least 5 kΩ with no more than 1 µF of capacitance.
Are the input channels on 6ES7334-0CE01-0AB0 isolated from the backplane?
The analog input channels are not electrically isolated from the backplane bus.
How quickly does 6ES7334-0CE01-0AB0 update all four input channels?
The maximum input cycle time for all channels is 5 ms.
Does 6ES7334-0CE01-0AB0 generate diagnostic alarms for signal faults?
The module has no alarm or diagnostic function, so the controller program must provide any required process plausibility checks.