Overview

Place of Origin:

USA

Brand Name:

HONEYWELL 

Model Number:

MC-PRHM01 51404109-175

Packaging Details:

Original new Factory Sealed

Delivery Time:

5-7 days

Payment Terms:

T/T

Supply Ability:

In stock

Specifications

Model:

MC-PRHM01 51404109-175

Product Type:

Remote Hardened Low Level Multiplexer

Dimensions:

3 × 31.4 × 27.8 cm

Weight:

0.52 kg

Input Channels:

32 galvanically isolated (16 per remote FTA)

Input Type:

Thermocouple; Linear millivolts

A/D Converter Resolution:

15 bits

Voltage Input Range:

0–100 mV

LSB (100 mV range):

8 µV

LSB (J/K/E thermocouples):

8 µV

LSB (T/B/S/R/R’ thermocouples):

2 µV

Common Mode Voltage:

±30 VRMS continuous (no damage); ±200 V intermittent

Crosstalk:

≥120 dB (dc to 60 Hz)

Input Impedance:

≥10 MΩ

Maximum Normal Mode Input:

±30 VRMS (continuous, one channel at a time)

Input Scan Rate:

Each channel once per 4 seconds

Line Frequency Noise Cancellation:

Configurable 50/60 Hz

Hardware Accuracy:

±0.075% FS

Software Accuracy:

0.1°C typical; 0.5°C max at 20°C

Surge Withstand Capability:

ANSI/IEEE C37.90.1-1978

CMRR:

90 dB min (1000 Ω lead resistance); 120 dB min (0 Ω lead resistance)

Reference Junction Accuracy:

±1°C max (20–25°C ambient)

Calibration Stability:

±50 ppm/°C max

Open Thermocouple Detection:

≤1000 Ω good; ≥1200 Ω PV = NAN

Max Loop Resistance:

1000 Ω total

Operating Temperature:

-40°C to +85°C (Remote FTA); 0°C to +50°C (IOP & power adapters)

Operating Humidity:

10–100% condensing (Remote FTA); 10–90% non-condensing (IOP/adapters)

Corrosives Rating:

Gx (Remote FTA); G1 or G3 (IOP/power adapters depending on option)

Description

The Honeywell MC-PRHM01 51404109-175 is a Remote Hardened Low Level Multiplexer. It switches and aggregates the minute signals generated by dispersed thermocouples or RTD sensors in harsh factory environments, transmitting the information to the control room via a single cable. This module is suitable for use in dusty, high-humidity areas with dispersed temperature measurement points.

Applications

Chemical Plants: Aggregate thermocouple signals from storage tanks and reactors to monitor feedstock temperature.

Power Plants: Transmit temperature data from boilers, steam pipelines, and bearing housings to prevent overheating.

Refineries: Collect high-temperature data from multiple stages of atmospheric/vacuum units and catalytic cracking towers to ensure processing safety.

Steel Mills: Track temperature changes in blast furnace walls, hot blast stoves, and ladles to avoid refractory burn-through.

Common Fault Handling

Channel PV shows NAN: The card checks disconnection each cycle. If thermocouple loop resistance >1000 Ω, check wiring; >1200 Ω is treated as open circuit and triggers NAN alarm.

Simultaneous loss of 16-channel group: Check remote FTA power supply and communication cables for failure or disconnection causing branch loss.

Periodic power-frequency noise in temperature signals: Check noise suppression settings and match hardware filter to grid frequency (50 Hz in China, 60 Hz for some equipment).

FAQ

Q: What are the channel count and input types of MC-PRHM01 51404109-175?
A: 32 isolated channels, supporting thermocouples and linear millivolt inputs.

Q: What are the resolution and voltage input range of MC-PRHM01 51404109-175?
A: 15-bit, 0–100 mV.

Q: What are the input impedance and hardware accuracy of MC-PRHM01 51404109-175?
A: ≥10 MΩ, accuracy ±0.075% FS.

Q: What are the scan rate and maximum loop resistance of MC-PRHM01 51404109-175?
A: One scan every 4 seconds, maximum loop resistance 1000 Ω.

Q: What is the operating temperature of the remote FTA for MC-PRHM01 51404109-175?
A: -40°C to +85°C.