SIEMENS · SINAMICS G120
6SL3225-0BE27-5AA1 SINAMICS G120 PM250 Power Module with Class A Filter
The SINAMICS G120 PM250 is a regenerative power module for 380 to 480 V three-phase supplies, rated at 11 kW for low-overload duty or 7.5 kW for high-overload duty.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6SL3225-0BE27-5AA1 |
| Product Type | PM250 regenerative power module with integrated Class A filter |
| Core Function | Supplies and controls a three-phase motor while returning braking energy to the line |
| Application or Compatible Series | SINAMICS G120 modular drive systems using a compatible Control Unit |
Exact Identification
Match 6SL3225-0BE27-5AA1 character by character and confirm the complete SINAMICS G120 PM250 Power Module with Class A Filter designation.
Interface Arrangement
Confirm the installed supply, ports, field connections and required accessories before wiring the replacement.
Configuration Check
Preserve the approved engineering project, network parameters and application data used by the installed system.
Product Overview
The SINAMICS G120 PM250 is a regenerative power module for 380 to 480 V three-phase supplies, rated at 11 kW for low-overload duty or 7.5 kW for high-overload duty.
The PM250 power stage can return braking energy to the incoming line without a separate braking resistor. The module supports low-overload and high-overload duty ratings so the drive can be selected for the required load profile. A Class A line filter is integrated into the power module for the documented industrial installation conditions.
Key Functions
Regenerative Power Stage
The PM250 power stage can return braking energy to the incoming line without a separate braking resistor.
Dual Load Ratings
The module supports low-overload and high-overload duty ratings so the drive can be selected for the required load profile.
Integrated EMC Filtering
A Class A line filter is integrated into the power module for the documented industrial installation conditions.
Official Specifications
| Line Supply | 3 AC 380 to 480 V ±10% |
|---|---|
| Line Frequency | 47 to 63 Hz |
| Rated Input Current, Low Overload | 25 A |
| Rated Input Current, High Overload | 19 A |
| Rated Output Voltage | 400 V according to IEC; 480 V according to NEC |
| Rated Power, Low Overload | 11 kW / 15 hp |
| Rated Power, High Overload | 7.5 kW / 10 hp |
| Rated Output Current, Low Overload | 25 A |
| Rated Output Current, High Overload | 19 A |
| Maximum Output Current | 38 A |
| Factory Pulse Frequency | 4 kHz |
| Vector-Control Output Frequency | 0 to 200 Hz |
| V/f-Control Output Frequency | 0 to 550 Hz |
| Maximum Shielded Motor Cable | 25 m |
| Maximum Unshielded Motor Cable | 100 m |
| Cooling Air Requirement | 0.038 m³/s |
| Ambient Temperature, Low Overload | 0 to 40 °C |
| Ambient Temperature, High Overload | 0 to 50 °C |
| Degree of Protection | IP20 / UL open type |
| Frame Size and Net Weight | FSC; 7.5 kg |
Frequently Asked Questions
Which supply network is required for 6SL3225-0BE27-5AA1?
Use a three-phase 380 to 480 V AC supply within the stated ±10% tolerance and 47 to 63 Hz frequency range.
What motor rating can 6SL3225-0BE27-5AA1 support?
The documented rating is 11 kW in low-overload duty or 7.5 kW in high-overload duty.
Can 6SL3225-0BE27-5AA1 return braking energy to the line?
Yes; the PM250 power stage is designed for energy recovery during regenerative operation.
How long can the shielded motor cable be with 6SL3225-0BE27-5AA1?
The maximum documented shielded motor-cable length is 25 m; the unshielded limit is 100 m.
Which enclosure protection applies to 6SL3225-0BE27-5AA1?
The power module is rated IP20 and UL open type, so it must be installed in a suitable enclosure.
What cooling provision is needed for 6SL3225-0BE27-5AA1?
Provide internal air cooling with the specified airflow and keep the ambient temperature within the applicable load-rating limit.
What should be checked before replacing 6SL3225-0BE27-5AA1?
Confirm the frame size, supply voltage, load duty, motor current, cable length, Control Unit compatibility and saved drive parameters.
Compatibility & Ordering Notes
Compatibility Checklist
- Pair the power module with a SINAMICS G120 Control Unit approved for the installed modular drive configuration.
- Check the line system, protective device, EMC installation and motor-cable length against the documented ratings.
- Back up drive parameters and verify the motor data before exchanging the power module.