Siemens SITOP RED1200 6EP4347-7RB00-0AX0 40 A redundantiae modululus
Fabricator: Siemens
Condición: Nuevo
Plazo de Entrega: En Stock
Origo: Austria
Garantía: 12 Meses
Inscriptio electronica: [email protected]
whatsapp: +86-18150117685
- Conspectus
- Product Overview
- Key Functions
- Official Specifications
- Quaestiones Frequenter Rogatae
- Compatibility & Ordering Notes
- Hot Selling Models
- Producta commendata
Conspectus
6EP4347-7RB00-0AX0 SITOP RED1200 Redundancy Module
Official Siemens technical data for decoupling two power supplies in redundant 24/48 V DC systems with up to 40 A total output.
Ad Primum Aspectum
| Nota | Siemens |
|---|---|
| Modellum | 6EP4347-7RB00-0AX0 |
| Typus Producti | SITOP RED1200 redundancy module |
| Functio principalis | Decouples two power supplies for a redundant DC feed |
| Application / Compatible Series | SITOP 24/48 V DC power systems |
Supply Pair
Confirm two suitable DC supplies and the required load current.
Voltage Window
Keep both input paths within the specified 10–58 V DC range.
Dispositio Thermica
Serva spatia montandi Siemens pro convectione naturali.
Product Overview
6EP4347-7RB00-0AX0 is officially identified by Siemens as SITOP RED1200 redundancy module with 24/48 V DC input and output for decoupling two SITOP power supplies with up to 20 A output current each.
The complete article number 6EP4347-7RB00-0AX0 should be matched against the installed hardware, nameplate and official project documentation. Similar products can differ in electrical ratings, interfaces, terminal design, packing quantity or approved system use.
Key Functions
Configuratio speciei specifica
6EP4347-7RB00-0AX0: Rated for 24/48 V DC input and output with 40 A total output capacity.
Interfacies Systematis
6EP4347-7RB00-0AX0: Separat duas SITOP fontes electricitatis, quae singulae usque ad 20 A currentem output producere possunt.
Substitutio controlis
6EP4347-7RB00-0AX0: Siemens indicat pondus netum 0,500 kg et dimensiones impacationis 185 × 190 × 80 mm.
Official Specifications
| Topologia Ingressus | Duo ingressus alimentationis disiuncti |
|---|---|
| Supple voltage | 12–48 V DC |
| Input voltage range | 10–58 V DC |
| Maxima Currus per Alimentationem | 20 A |
| Numerus Exitus | 1 |
| Tensio Egressus | Tensio ingressus minus approximative 0.6 V |
| Currentis Output Aestimatus | 40 A |
| Adjustabilis Exitus | No |
| Coniunctio Apparatum | No |
| Efficacia | 97.5% |
| Amissa Potentia ad Currum Nominalem | Typice 25 W |
| Amor fatuae | Maximum 0.1 W |
| Isolatio galvanica | No isolation between input and output |
| Classis Protectionis | Classis III |
| Gradus praesidium | IP20 |
| Normae EMC | EN 61000-6-3 emissions; EN 61000-6-2 immunity |
| Temperatura operativa | −40 to +70 °C, natural convection |
| Storage / Transport Climate | −40 to +85 °C; climate class 3K3, 5–95% non-condensing |
| Connection Data | Push-in terminals; 0.75–16 mm² for each input and output |
| Installatio mechanica | 45 × 135 × 125 mm; 35 mm DIN rail; 45 mm clearances above and below |
Quaestiones Frequenter Rogatae
How many power supplies can 6EP4347-7RB00-0AX0 decouple?
It decouples two DC power supplies, with a maximum of 20 A from each input path.
What input-voltage window must be maintained for 6EP4347-7RB00-0AX0?
The permissible input range is 10–58 V DC for systems with a 12–48 V DC supply voltage.
What output can engineers expect from 6EP4347-7RB00-0AX0?
One output supplies up to 40 A; its voltage is the input voltage minus approximately 0.6 V.
Does 6EP4347-7RB00-0AX0 provide galvanic isolation?
No. Input and output are not galvanically isolated, so the protective and grounding concept must account for the common DC circuit.
How should 6EP4347-7RB00-0AX0 be mounted for cooling?
Snap it onto a 35 mm DIN rail and maintain 45 mm free space above and below for natural convection.
Which conductors fit the terminals of 6EP4347-7RB00-0AX0?
Terminales de entrada y salida por inserción aceptan secciones transversales de conductor desde 0,75 hasta 16 mm².
¿Qué entorno operativo se especifica para el 6EP4347-7RB00-0AX0?
La operación por convección natural se especifica desde −40 hasta +70 °C, con clase climática 3K3 y humedad relativa del 5 al 95 % sin condensación.
Compatibility & Ordering Notes
Index Compatibilitatis pro 6EP4347-7RB00-0AX0
- Concorda cum numero articuli integro 6EP4347-7RB00-0AX0, sine abbreviatione sufficii.
- Confirma systema SITOP RED1200 installatum et revisionem hardware.
- Verifica: Certificatum pro 24/48 V DC inpu et output, cum capacitate output totali 40 A.
- Confirma terminales, connectores et accessoria inclusa in citatione scripta.