Siemens SIMATIC S7-400 6ES7405-0KA02-0AA0 PS 405 10 A Power Supply
Fabricator: Siemens
Condición: Nuevo
Plazo de Entrega: En Stock
Origo: Germania
Garantía: 12 Meses
Inscriptio electronica: [email protected]
whatsapp: +86-18150117685
- Conspectus
- Product Overview
- Key Functions
- Official Specifications
- Quaestiones Frequenter Rogatae
- Compatibility & Ordering Notes
- Hot Selling Models
- Producta commendata
Conspectus
SIEMENS · SIMATIC S7-400
6ES7405-0KA02-0AA0 PS 405 10 A Power Supply
Siemens 6ES7405-0KA02-0AA0 is a SIMATIC S7-400 PS 405 wide-range DC power-supply module for rack installations that require 10 A on the 5 V backplane rail.
Ad Primum Aspectum
| Nota | Siemens |
|---|---|
| Modellum | 6ES7405-0KA02-0AA0 |
| Typus Producti | PLC rack power-supply module |
| Functio principalis | Converts 24/48/60 V DC input into S7-400 backplane power |
| Applicatio vel series compatibiles | SIMATIC S7-400, S7-400H and S7-400F/FH systems |
DC Source Check
Verify the nominal 24 V, 48 V or 60 V DC supply and its permitted tolerance.
Backplane Load
Calculate the rack current required on both the 5 V and 24 V outputs.
Retentive Backup
Adapt the optional two-cell lithium backup arrangement to the installed system.
Product Overview
Siemens 6ES7405-0KA02-0AA0 is a SIMATIC S7-400 PS 405 wide-range DC power-supply module for rack installations that require 10 A on the 5 V backplane rail.
The supply accepts 24 V, 48 V or 60 V DC nominal input across a broad static range. The unit supplies both 5.1 V DC and 24 V DC backplane rails. It bridges short input interruptions and provides optional battery backup for retained data.
Key Functions
Wide-Range DC Input
The supply accepts 24 V, 48 V or 60 V DC nominal input across a broad static range.
S7-400 Rack Outputs
The unit supplies both 5.1 V DC and 24 V DC backplane rails.
Buffered Operation
It bridges short input interruptions and provides optional battery backup for retained data.
Official Specifications
| Tensio Input Nominale | 24 V, 48 V or 60 V DC |
|---|---|
| Intervalum Inpūtātiōnis Staticum | 19.2 ad 72 V DC |
| Campus Input Dynamicus | 18.5 usque ad 75.5 V DC |
| Evaluatus Input Correntia | 4.0 A ad 24 V; 2.0 A ad 48 V; 1.6 A ad 60 V |
| Cursus Impulsivus | 18 A culmen cum latitudine semi-valoris 20 ms |
| Tensiones Exeuntes | 5,1 V DC et 24 V DC |
| Currentes Exirentes | 10 A ad 5 V DC et 1,0 A ad 24 V DC |
| Potentiae-Defectus Buffering | Plus quam 20 ms ad ritmum repetitionis 1 s |
| Consumptio potentiae | 95 W |
| Ammissio Potentiae | 20 W |
| Backup Current | Maximum 100 µA cum potentia intrante ex |
| Batteriae auxiliares optionales | 2 cellulae lithii AA, 3.6 V / 2.3 Ah utraque |
| Classis Protectionis | Classis I cum conductore protectivo |
| Categoria Super Voltae | II |
| Gradus Contaminations | 2 |
| Separatio protectiva | According to IEC 61131-2 |
| Interstitia Armaturae Requiruntur | 2 |
| Dimensiones | 50 × 290 × 217 mm (lat × alt × prof) |
| Pondus Approximatum | 1.2 kg |
Quaestiones Frequenter Rogatae
Quae fons DC alere potest 6ES7405-0KA02-0AA0?
Modulus accipit nominalem 24 V, 48 V aut 60 V DC intra limites suos introductus documentatos.
Quod effusum dorsale 6ES7405-0KA02-0AA0 praebet?
The supply provides 10 A at 5 V DC plus 1.0 A at 24 V DC.
Does 6ES7405-0KA02-0AA0 need two free rack slots?
The unit occupies two positions in the S7-400 rack.
How should I account for startup current on 6ES7405-0KA02-0AA0?
Select the upstream DC source and protection to tolerate the specified 18 A inrush pulse.
Will 6ES7405-0KA02-0AA0 ride through a brief voltage dip?
The supply buffers interruptions for more than 20 ms under the documented condition.
How is data retention supported by 6ES7405-0KA02-0AA0?
The optional backup uses two 3.6 V lithium AA cells rated at 2.3 Ah each.
What must be isolated before replacing 6ES7405-0KA02-0AA0?
Remove the DC input, isolate the rack and verify the backplane is de-energized before withdrawing the module.
Compatibility & Ordering Notes
Index Compatibilitatis
- Do not substitute a PS 407 AC-input unit for this DC-input power supply.
- Confirm the 5 V and 24 V load totals remain within the stated output limits.
- Transfer backup batteries only with the rack safely isolated and the retention plan understood.