Siemens 6ES7157-1AB00-0AB0 SIMATIC ET 200AL IM 157-1 PN Interface Module
Fabricator: Siemens
Condición: Nuevo
Plazo de Entrega: En Stock
Origo: Germania
Garantía: 12 Meses
Inscriptio electronica: [email protected]
whatsapp: +86-18150117685
- Conspectus
- Hot Selling Models
- Producta commendata
Conspectus
- Verify the PROFINET controller project and station I/O allocation before commissioning.
- Utere dispositionibus connectorum Ethernet M12 et ET/alimentationis M8 requisitis.
- Serva planum redundantiae mediis separatum a requisitis redundantiae systematis S2/R1.
- Verifica softwarem ingeniariae installatum et versionem GSDML ante substitutionem.
6ES7157-1AB00-0AB0 SIMATIC ET 200AL IM 157-1 PN Interface Module
IM 157-1 PN with a two-port M12 PROFINET interface, IRT and Shared Device support in an IP65/IP67 ET 200AL housing.
Ad Primum Aspectum
| Nota | Siemens |
|---|---|
| Modellum | 6ES7157-1AB00-0AB0 |
| Typus Producti | Distributed I/O interface module |
| Functio principalis | Connecting an ET 200AL station to PROFINET IO |
| Applicatio | Compact machine-level distributed I/O networks |
PROFINET station access
Connects distributed ET 200AL I/O through an integrated two-port switch with 100BASE-TX full-duplex operation.
Usus statio communis
Apparatus communis ad usum usque ad quattuor regulatores IO patet.
Continuitas rete
Functio MRP et MRPD redundantiae mediorum, simul cum communicatione IRT et initio prioritario.
Product Overview
6ES7157-1AB00-0AB0 Coniungit stationem ET 200AL ad regulatorem PROFINET IO per duos portus Ethernet M12 D-codificatos cum commutatore integrato.
Modulus functio IRT, Apparatum Communem et redundantiam mediorum sustinet; tamen configuratio technica has proprietates rete a redundantia systematis S2 vel R1 non suffultis distinguit.
Key Functions
PROFINET station access
Connects distributed ET 200AL I/O through an integrated two-port switch with 100BASE-TX full-duplex operation.
Usus statio communis
Apparatus communis ad usum usque ad quattuor regulatores IO patet.
Continuitas rete
Functio MRP et MRPD redundantiae mediorum, simul cum communicatione IRT et initio prioritario.
Official Specifications
| Rated supply / permissible range | 24 V DC / 20,4–28,8 V DC |
|---|---|
| Currentus Subministratiōnis Sine Onere | 100 mA |
| Maxima Currus Suppeditandus | 4 A pro 1L+ et 4 A pro 2L+ |
| Perditio potentiæ typica | 2,9 W |
| Maximum station address space | 1,430 bytes |
| Conexión PROFINET | 1 interfacies cum 2 portibus M12 D-codificatis et commutatore integrato |
| Transmissio Ethernet industrialis | 100BASE-TX, 100 Mbit/s, duplex plenus |
| Intervalla horologiae IRT mittendae | 250 µs, 500 µs, 1, 2, 4, 8, 16, 32, 64 et 128 ms |
| Modus I/O isochronus | Non sustentatum |
| Apparatus Communis | Usque ad 4 controllores IO |
| Redundantia Mediorum | MRP et MRPD suffragati |
| Redundantia Systematis | S2 et R1 non suffragati |
| Ipsum Support | Versio TIA Portal V13 SP1 aut posterior; STEP 7 V5.5 SP4 cum Hotfix 3 aut posterior |
| GSDML | Versio 2.3.1 |
| Network Management Protocols | TCP/IP, SNMP et LLDP |
| Indicatio status | LED RUN, ERROR, MAINT et 2 LED de liaison |
| Aestimatio Protectionis | IP65/IP67 |
| Temperatura operativa | −25 ad +55 °C |
| Dimensiones (L × H × D) | 45 × 159 × 40 mm |
| Pondus Approximatum | 263 g |
Quaestiones Frequenter Rogatae
Combien de ports physiques PROFINET le modèle 6ES7157-1AB00-0AB0 fournit-il ?
Son unique interface PROFINET comporte deux ports M12 à code D, reliés via un commutateur intégré.
Quatre contrôleurs peuvent-ils partager la station d’E/S grâce au modèle 6ES7157-1AB00-0AB0 ?
La fonction Shared Device prend en charge jusqu’à quatre contrôleurs d’E/S, à condition que la configuration de génie logiciel attribue les droits d’accès en conséquence.
La prise en charge d’IRT signifie-t-elle que le modèle 6ES7157-1AB00-0AB0 prend en charge le mode E/S isochrone ?
La communication IRT est prise en charge, mais le mode E/S isochrone ne l’est pas.
Can 6ES7157-1AB00-0AB0 be selected for S2 system redundancy?
The interface does not support S2 or R1 system redundancy.
Which media-redundancy functions are available on 6ES7157-1AB00-0AB0?
Both MRP and MRPD are supported.
What is the minimum TIA Portal version for 6ES7157-1AB00-0AB0?
The specified engineering support begins with TIA Portal V13 SP1.
Can 6ES7157-1AB00-0AB0 operate at −30 °C?
The specified operating range starts at −25 °C and extends to +55 °C.