Siemens 6ES7133-0BH01-0XB0 SIMATIC ET 200B 8DI 8DO Digital Electronics Block
Fabricator: Siemens
Condición: Nuevo
Plazo de Entrega: En Stock
Origo: Germania
Garantía: 12 Meses
Inscriptio electronica: [email protected]
whatsapp: +86-18150117685
- Conspectus
- Hot Selling Models
- Producta commendata
Conspectus
- Retain the compatible DC terminal block and its permanent field wiring.
- Limit the eight-output group to 2 A and each individual output to 0.5 A.
- Match SYNC/FREEZE usage and PROFIBUS speed to the master configuration.
- Use the appropriate screw or spring-terminal arrangement for the existing three- or four-wire field connections.
6ES7133-0BH01-0XB0 SIMATIC ET 200B 8DI 8DO Digital Electronics Block
An ET 200B electronics block with eight 24 V inputs, eight 0.5 A outputs and a PROFIBUS connection up to 12 Mbit/s.
Ad Primum Aspectum
| Nota | Siemens |
|---|---|
| Modellum | 6ES7133-0BH01-0XB0 |
| Typus Producti | Mixed digital I/O electronics block |
| Functio principalis | Acquiring discrete inputs and switching DC loads |
| Applicatio | ET 200B PROFIBUS installations |
Combine input and output signals
Eight DC inputs and eight DC outputs serve a mixed local signal group.
Switch small DC loads
Each output supports up to 0.5 A, with electronic short-circuit protection and a 2 A group limit up to 60 °C.
Coordinate PROFIBUS I/O
The block supports SYNC and FREEZE services and provides separate channel, RUN and bus-fault indicators.
Product Overview
6ES7133-0BH01-0XB0 combines eight digital inputs and eight transistor outputs in one ET 200B electronics block. It connects the local signals to a PROFIBUS DP network at rates up to 12 Mbit/s.
The electronics fit the corresponding DC terminal blocks so that field wiring can remain on the terminal assembly. Electronic short-circuit protection, channel indicators and RUN/BF LEDs support commissioning and service.
Key Functions
Combine input and output signals
Eight DC inputs and eight DC outputs serve a mixed local signal group.
Switch small DC loads
Each output supports up to 0.5 A, with electronic short-circuit protection and a 2 A group limit up to 60 °C.
Coordinate PROFIBUS I/O
The block supports SYNC and FREEZE services and provides separate channel, RUN and bus-fault indicators.
Official Specifications
| Dispositio canalium digitalium | octo introitus et octo exitus |
|---|---|
| Supply rating and continuous range | 24 V DC; 18.5–30.2 V DC |
| Currentia logica typica ab L3+ | 70 mA |
| Maximum sensor supply current from L3+ | 500 ma |
| Maxima Pēnsum Perditiōnis | 3,8 W |
| Limina Signali Inputii | Signum 0: −30 usque +5 V; signum 1: 13–30 V |
| Currentis signali intrantis | 4 mA typice; minimum 2 mA ad 24 V |
| Tempus morae intrantis ad ascensum | 2–3 ms |
| Longitudo maxima cavi I/O non scuti | 100 m |
| Valor Currentis Exirentis | 0.5 A per canallem; maximum 2 A per gruppus usque ad 60 °C |
| Fugatio output in statu off | Maximum 1 mA |
| Minima tensio outputi in statu ON | Supply voltage minus 3 V |
| Resistive-Load Output Delays | Maximum 20 µs in statu on; maximum 0.5 ms in statu off |
| Frequentias maximas de commutatione | 100 Hz resistivum; 0.5 Hz inductivum; 8 Hz onus lampae |
| Maxima onus lampadis | 5 W per outputum |
| Maximum PROFIBUS Transmission Rate | 12 Mbit/s |
| Isolement de potentiel | Blocus electronicus isolatus a PROFIBUS DP; canales non inter se isolati |
| Temperatura operativa | 0–60 °C horizontaliter; usque ad 40 °C in aliis positionibus |
| Humiditas Operandi | 15–95% umiditas relativa |
| Dimensio et massa combinata electronicae et terminalis | 160 × 130 × 60 mm; circiter 650 g |
Quaestiones Frequenter Rogatae
Quae basia terminalium cum 6ES7133-0BH01-0XB0 uti possum?
Fragmen electronicum aptatur ad TB1/DC, TB1-4/DC, TB3/DC et TB3-4/DC.
Num omnes exitus 6ES7133-0BH01-0XB0 ad 0.5 A simul onerare possum?
Gruppus octo-exituum limitatur ad 2 A combinatos usque ad 60 °C.
Num 6ES7133-0BH01-0XB0 suadet PROFIBUS SYNC et FREEZE?
Hoc frustum utrumque servitium SYNC et FREEZE sustinet.
Num 6ES7133-0BH01-0XB0 onus inductivum eodem ritmo quam onus resistivum commutare potest?
Frequentia maxima pro oneribus inductivis est 0.5 Hz, at pro oneribus resistivis 100 Hz.
Quae fuga sensoris permittitur in input duorum filorum 6ES7133-0BH01-0XB0?
Maxima quiescens currentia sensoris duorum filorum est 1.5 mA.
Quomodo defectum bus in 6ES7133-0BH01-0XB0 agnoscere possum?
Indicator ruber BF defectum bus separatim ab indicatoribus RUN et status canalis nuntiat.
Num 6ES7133-0BH01-0XB0 verticaliter ad 60 °C operari possum?
Orientations montandi praeter horizontalem ad 40 °C tantum limitantur.