Siemens 6ED1052-2CC08-0BA2 LOGO! 24CEo Logic Module without Display
Fabricator: Siemens
Condición: Nuevo
Plazo de Entrega: En Stock
Origo: Germania
Garantía: 12 Meses
Inscriptio electronica: [email protected]
whatsapp: +86-18150117685
- Conspectus
- Hot Selling Models
- Producta commendata
Conspectus
- Use LOGO! Soft Comfort V8.4 or later for the 0BA2 basic module.
- Allocate analog input functions within the eight onboard input positions.
- Keep transistor loads within the output-current rating.
- Use the Ethernet, web and microSD features required by the application without substituting a relay-output or display-equipped hardware variant.
6ED1052-2CC08-0BA2 LOGO! 24CEo Logic Module sine display
Un LOGO! 24CEo sine display, cum octo intrationes, quattuor effusiones transistorum, Ethernet, functiones web, et conectivitas LOGO! 8.4 MQTT.
Ad Primum Aspectum
| Nota | Siemens |
|---|---|
| Modellum | 6ED1052-2CC08-0BA2 |
| Typus Producti | Compact logic module |
| Functio principalis | Logica programmabilis et temporis regulatio |
| Applicatio | Systemata modularia automationis LOGO! |
Usus combinatus intrationum digitalium et analogarum
Quattuor ex octo intrationibus in modo analogico 0–10 V operari possunt, non in modo digitali.
Functiones rete et web
Ethernet, servus web integratus, pagine web a usuario definitae, et supportus MQTT applicationem LOGO! 8.4 ad functiones rete coniungunt.
Logica programmabilis compacta
Modulus praebet memoriam pro usque ad 400 blocos functionum cum expansione modulari et supporto standardis microSD.
Product Overview
6ED1052-2CC08-0BA2 praebet configurationem LOGO! 24CEo sine display integrato.
Octo eius intritus includunt quattuor positiones utiles pro signis analogicis, dum Ethernet, servus web integratus, registratio datorum et supportum microSD praebent functiones communicationis et datorum in modulo logico compacto.
Key Functions
Usus combinatus intrationum digitalium et analogarum
Quattuor ex octo intrationibus in modo analogico 0–10 V operari possunt, non in modo digitali.
Functiones rete et web
Ethernet, servus web integratus, pagine web a usuario definitae, et supportus MQTT applicationem LOGO! 8.4 ad functiones rete coniungunt.
Logica programmabilis compacta
Modulus praebet memoriam pro usque ad 400 blocos functionum cum expansione modulari et supporto standardis microSD.
Official Specifications
| Copia | 24 V DC; permisum 20.4–28.8 V DC |
|---|---|
| Intrinseci introitus. | 8 intritus digitalis; 4 potest pro signis analogicis 0–10 V uti |
| Output onboard | 4 transistor outputs |
| Currentia maxima emissa | 0,3 A per exitum ad temperaturis 0–55 °C |
| Protectio contra curtum circuitum in effluenti | Electronicus, 1 A |
| Capacitas Programmatum | Up to 400 function blocks |
| Horologii potentiae reservae | 480 h |
| Network Connection | Aethernet |
| Interfacs web | Servus web integratus cum paginis web definitis ab usu |
| Removable Storage | MicroSD card standardis |
| Monitor incorporatus | Nullus |
| Montatio | 35 mm DIN-rail |
| Temperatura operativa | −20 ad +55 °C, sine condensatione |
| Temperatura servandi et transportandi | −40 usque ad +70 °C |
| Dimensiones | 71,5 × 90 × 58 mm |
| Emissio radiointerferentiae | EN 55011, classis B |
Quaestiones Frequenter Rogatae
Num 6ED1052-2CC08-0BA2 includit display pro programmatione locali?
Hoc est LOGO! 24CEo basicum modulum sine monstratore.
Possuntne omnes octo introitus in 6ED1052-2CC08-0BA2 manere digitales, etiam si signa analogica connectuntur?
Canalia analogica quattuor ex octo positionibus introituum reutilizant, non autem novos introitus addunt.
Suntne exitus 6ED1052-2CC08-0BA2 contactus rellay?
Modulus quattuor exitus transistoris habet.
Quam versionem programmatum ad ingenium 6ED1052-2CC08-0BA2 utendam eligere debo?
Utere LOGO! Soft Comfort V8.4 vel posteriorem.
Potestne 6ED1052-2CC08-0BA2 communicationem MQTT supportare?
MQTT in LOGO! 8.4 unitate basica disponibilis est.
Possumne paginas personalis navigatoris pro applicatione per 6ED1052-2CC08-0BA2 praebere?
The integrated web server supports user-defined web pages.
How long can the switching clock of 6ED1052-2CC08-0BA2 bridge a power interruption?
The specified clock power reserve is 480 hours.