Overview
SIEMENS · SIMATIC S7-400 FM 458-1 DP
6DD1607-0EA0 SIMATIC S7-400 EXM 448 Communications Expansion Module
The EXM 448 expands an FM 458-1 DP application with a configurable PROFIBUS-DP interface and a slot for an approved MASTERDRIVES option module.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6DD1607-0EA0 |
| Product Type | EXM 448 communications expansion module |
| Core Function | Adds configurable high-speed PROFIBUS-DP communication to the FM 458-1 DP |
| Application or Compatible Series | SIMATIC S7-400 FM 458-1 DP applications and supported MASTERDRIVES options |
Exact Identification
Match 6DD1607-0EA0 character by character and confirm the complete SIMATIC S7-400 EXM 448 Communications Expansion Module designation.
Interface Arrangement
Confirm the installed supply, ports, field connections and required accessories before wiring the replacement.
Configuration Check
Preserve the approved engineering project, network parameters and application data used by the installed system.
Product Overview
The EXM 448 expands an FM 458-1 DP application with a configurable PROFIBUS-DP interface and a slot for an approved MASTERDRIVES option module.
The integrated interface can be configured as a DP master or DP slave and supports Shared Input, SYNC and FREEZE functions. The LE bus provides fast data transfer between the FM 458-1 DP and its expansion modules, while the P bus supplies the module. A dedicated RS232 parameterization interface and two communication-status LEDs support setup and diagnostics.
Key Functions
Configurable PROFIBUS-DP Interface
The integrated interface can be configured as a DP master or DP slave and supports Shared Input, SYNC and FREEZE functions.
Expansion-Module Data Path
The LE bus provides fast data transfer between the FM 458-1 DP and its expansion modules, while the P bus supplies the module.
Service and Status Access
A dedicated RS232 parameterization interface and two communication-status LEDs support setup and diagnostics.
Official Specifications
| PROFIBUS-DP Connector | X1, floating RS485 interface |
|---|---|
| PROFIBUS Operating Modes | Master or slave |
| Supported DP Functions | Shared Input, SYNC and FREEZE |
| Transfer-Rate Range | 9.6 kbit/s to 12 Mbit/s |
| Maximum Number of Slaves | 127, depending on the configuration |
| Maximum Telegram Length | 244 bytes per slave |
| Parameterization Interface | RS232 |
| Status Indicators | 2 LEDs for the communication interface and bus activity |
| Expansion Bus | LE bus for high-speed transfer with FM 458 expansion modules |
| Backplane-Bus Function | P bus used only for power supply |
| External 5 V Load | Maximum 90 mA; not short-circuit proof |
| Rated Internal Voltage | +5 V DC |
| Typical Current Consumption | 0.3 A |
| Typical Power Loss | 1.5 W |
| Maximum Ambient Temperature | 40 °C |
| Module Width | 1 slot |
| Dimensions (W × H × D) | 25 × 290 × 210 mm |
| Approximate Weight | 0.85 kg |
Frequently Asked Questions
Which controller platform accepts 6DD1607-0EA0?
Install it as an expansion module for the FM 458-1 DP and preserve the rack and project configuration used by the existing application.
Can 6DD1607-0EA0 operate as either a PROFIBUS master or slave?
Yes; the interface is configurable for either operating mode, so the replacement must use the same role and bus parameters as the installed unit.
What network capacity should be considered for 6DD1607-0EA0?
The interface supports rates from 9.6 kbit/s to 12 Mbit/s and up to 127 slaves, subject to the engineered configuration.
Where should 6DD1607-0EA0 be installed?
Use it only inside a closed switch cabinet and keep the ambient temperature within the specified limit.
How can communication be checked on 6DD1607-0EA0?
Use the two front indicators to confirm the communication-interface state and bus activity, then compare the configured DP role and rate.
What limit applies to the external 5 V output on 6DD1607-0EA0?
The external load must not exceed 90 mA, and the output is not short-circuit proof.
What should be preserved before replacing 6DD1607-0EA0?
Back up the FM 458 configuration, PROFIBUS parameters, master or slave assignment, address data and any installed option-module settings.
Compatibility & Ordering Notes
Compatibility Checklist
- Use the module with the matching FM 458-1 DP hardware configuration and documented expansion-bus arrangement.
- Retain the PROFIBUS operating role, station address, transfer rate and telegram configuration during replacement.
- Verify the installed MASTERDRIVES option module and restore its application parameters from the approved project backup.