Siemens SIMATIC ET 200SP 6ES7677-2DB42-0GB0 CPU 1515SP PC2 Open Controller
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Product Overview
- Key Functions
- Official Specifications
- Frequently Asked Questions
- Compatibility & Ordering Notes
- Hot Selling Models
- Recommended Products
Overview
SIEMENS SIMATIC ET 200SP
6ES7677-2DB42-0GB0 CPU 1515SP PC2 Open Controller
An ET 200SP Open Controller combining an industrial PC environment with an S7-1500 Software Controller in one compact distributed-I/O platform.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7677-2DB42-0GB0 |
| Product Type | CPU 1515SP PC2 Open Controller |
| Core Function | Runs PC applications and deterministic machine control on one platform |
| Compatible Series | SIMATIC ET 200SP |
Exact Identification
Match the full article number, FS04 hardware level, installed firmware and CFast image.
Interface Arrangement
Confirm the ET 200SP BusAdapter, Gigabit Ethernet, USB and DisplayPort connections used by the machine.
Configuration Check
Preserve the controller project, Windows setup, licenses and 128 GB CFast restore image before replacement.
Product Overview
The CPU 1515SP PC2 combines a Windows-based industrial PC with the CPU 1505SP S7-1500 Software Controller. The supplied 128 GB CFast card contains Windows 10 IoT Enterprise LTSC 2019, the controller runtime and a restore image.
Integrated ET 200SP BusAdapter connectivity, Gigabit Ethernet, USB 3.0, USB 2.0 and DisplayPort support automation, service and PC-side applications within a compact ET 200SP station.
Key Functions
Combined PC and PLC Operation
Runs Windows-based applications alongside the CPU 1505SP Software Controller on one device.
Direct ET 200SP Integration
Connects to distributed I/O through the dedicated ET 200SP BusAdapter PROFINET interface.
Restorable System Storage
Uses a 128 GB CFast card that carries the operating system, controller software and restore image.
Service and Peripheral Access
Provides Gigabit Ethernet, four USB ports and DisplayPort for network, maintenance and display connections.
Official Specifications
| Hardware Function Status | FS04 or later |
|---|---|
| Firmware Version | V20.8 |
| TIA Portal Engineering | Configurable from STEP 7 TIA Portal V16 |
| Installed Operating System | Windows 10 IoT Enterprise LTSC 2019, 64-bit |
| Visualization Software | Not installed |
| Processor | Intel Atom E3940, 1.6 GHz, 4 cores |
| Main Memory | 8 GB DDR3L RAM |
| CFast Storage | 128 GB flash memory |
| Integrated Work Memory | 1 MB for program and 5 MB for data |
| Supply Voltage Range | 19.2–28.8 V DC, nominal 24 V DC |
| Reverse-Polarity Protection | Supported |
| Power-Failure Buffer Time | 5 ms |
| Rated Input Current | 1.8 A at full processor load including ET 200SP modules and USB use |
| Maximum Input Current | 2.9 A |
| Maximum Active Power Input | 43 W including ET 200SP modules and USB use |
| Typical Power Loss | 16 W |
| Ethernet Interface | 1 × 10/100/1000 Mbps |
| USB Interfaces | 2 × USB 3.0 and 2 × USB 2.0 |
| Display Interface | 1 × DisplayPort |
| Removable-Media Interfaces | 1 × CFast slot and 1 × SD/MMC slot |
Frequently Asked Questions
Is a visualization runtime preinstalled on 6ES7677-2DB42-0GB0?
No, visualization software is not installed on this controller configuration.
From which TIA Portal version can 6ES7677-2DB42-0GB0 be engineered?
Use STEP 7 TIA Portal V16 or a later compatible release.
How should the CFast restore image for 6ES7677-2DB42-0GB0 be protected?
Keep a verified backup of the supplied 128 GB CFast image together with the controller project and required licenses.
Can 6ES7677-2DB42-0GB0 operate without a SIMATIC Memory Card?
Yes, a SIMATIC Memory Card is not required for this configuration.
How long can 6ES7677-2DB42-0GB0 bridge a brief power interruption?
The specified stored-energy time for a mains or voltage failure is 5 ms.
What current capacity should be allowed when powering 6ES7677-2DB42-0GB0?
Design the 24 V DC supply for up to 2.9 A while accounting for connected ET 200SP modules and USB devices.
Which local service connections are available on 6ES7677-2DB42-0GB0?
The unit provides Gigabit Ethernet, two USB 3.0 ports, two USB 2.0 ports and one DisplayPort.
Compatibility & Ordering Notes
Compatibility Checks
- Confirm the STEP 7 TIA Portal release and installed hardware support package.
- Back up the controller project, Windows configuration, licenses and CFast restore image.
- Verify the 24 V DC supply and connected ET 200SP module load.
- Match the BusAdapter, Ethernet addressing, USB devices and display connection.